HP 253449-B21 Leaflet
14
3Phase power solutions (UPS, PDR)
HP 3Phase UPS Modules (Rackmount)
Model
R8000/3 Intl
R12000/3 Intl
Part number
AF432A
AF430A
Form factor
Rack module/6U
Rack module/6U
INput power
INput connections (INTL model)
INput connections (INTL model)
400 V 3phase
1 x IEC 309 16A (3phase power)
1 x IEC 309 16A (3phase power)
400 V 3phase
1 x IEC 309 32A (3phase power)
1 x IEC 309 32A (3phase power)
OUTput power rating/capacity
8 kVA/8 kW; 400 V 3phase
12 kVA/12 kW; 400 V 3phase
OUTput connections (INTL model)
1 x IEC 309 16A (3phase power)
2 x IEC 309 16A (3phase power) = UPS output module
(AF434A)
(AF434A)
Backup time at 80% load
1
12 mins
6 mins
Hot-swap electronic modules & batteries Yes Yes
Weight (kg)
140
140
Optional ERM/part number
max. 4/AF434A
max. 4/AF434A
Communication
HP UPS Management module (AF401A) included; module with one ethernet port and five serial ports (RJ45)
Communication software
Embedded HP Power Management software on HP UPS Management module (AF401A)
Warranty
3-Year HP warranty (3-1-1), HP battery pre-failure warranty and integrated Care Pack Support at no additional
cost
cost
HP 3Phase Parallel UPS (preconfigured Rack & module)
Model
RP36000/3 Intl
RP12000/3 Intl
Description
Preconfigured parallel rack UPS
Rack 42U with three UPS modules and power bar
Rack 42U with three UPS modules and power bar
Additional 12 kVA UPS module for RP36000/3 (to be
added into the parallel rack UPS (RP36000/3))
added into the parallel rack UPS (RP36000/3))
Part number
AF439A
AF437A
Form factor
Rack 42U (HP 10000 Series G2, 10642)
Rack module/6U
INput power
INput connections (intl model)
INput connections (intl model)
400 V 3phase
Hard wire terminal
Hard wire terminal
400 V 3phase
to power bus bar (on RP36000/3)
to power bus bar (on RP36000/3)
OUTput power rating/capacity
non-redundant: 36 kVA/36 kW
n+1 redundant: 24 kVA/24 kW – expandable up to
60 kVA (n+1)
n+1 redundant: 24 kVA/24 kW – expandable up to
60 kVA (n+1)
12 kVA/12 kW; 400 V 3phase
OUTput connections (intl model)
Hard wire terminal; Optional (add on): HP R12000/3
Intl UPS Output Module (AF441A)
Intl UPS Output Module (AF441A)
Connector to power bus bar (on RP36000/3) or
optional: UPS output module (AF441A)
optional: UPS output module (AF441A)
INput power
INput connections (intl model)
INput connections (intl model)
400 V 3Phase
1 x IEC309 16A (3Phase power)
1 x IEC309 16A (3Phase power)
400 V 3Phase
1 x IEC309 32A (3Phase power)
1 x IEC309 32A (3Phase power)
Backup time at 80% load
1
12 mins
6 mins
Hot-swap electronic modules & batteries Yes
Yes
Weight (kg)
578
140
Optional ERM/part number
AF434A
max. 4/AF434A
Communication
HP UPS Management module (AF401A) included; module with one ethernet port and five serial ports (RJ45)
Communication software
Embedded HP Power Management software on HP UPS Management module (AF401A)
Warranty
3-Year HP warranty (3-1-1), HP battery pre-failure warranty
HP 3Phase power solutions
New zoned power approach with power protection and power distribution for zone/rack row level
• Adding power protection and distribution capacity when and where needed
• Adding power protection and distribution capacity when and where needed
• Getting the reliability of large central systems in a rack footprint
• Enable adding capacity to otherwise full data centres
• High energy-efficiency (97% efficient)
HP 3Phase UPS solutions – 3Phase UPS modules and Parallel UPS (preconfigured UPS Rack)
• UPS modules with 8 kVA and 12 kVA capacity
• Parallel UPS with 36 kVA capacity – scalable up to 60 kVA in a single 19" rack
• High-density design, lightweight, hot-swappable battery and electronics modules
• Intelligent automated maintenance bypass in each UPS module/chassis
• Integrated Care Pack Support for the single Rack UPS modules (R8000/3 and R12000/3) – HP Server
and Storage Care Pack supports HP UPSs up to 12 kVA at no additional cost