Geist I20004 User Manual

Page of 3
Part Number
I20004 -- MN02X4W1-36PT68-3PS6B0A10-S
Upgradeable, Power Unit Level Monitoring
Power Configuration
30A, 208V, 4.9kW
Physical Configuration
72 in / 1829 mm Vertical
Description
The I20004 -- MN02X4W1-36PT68-3PS6B0A10-S upgradeable power monitoring PDU
delivers comprehensive view of power usage in a data center with Geist’s Interchangeable
Monitoring Device (IMD). The modular design of the PDU allows the “hot-swappable” IMD
to be upgraded as new technology is developed. 
With its current IMD, the I20004 -- MN02X4W1-36PT68-3PS6B0A10-S offers on-board and
web power monitoring display options with quick access to the unit's current, volts, real
power, apparent power, power factor and kilowatt hours. By monitoring these critical
variables, data center managers can evaluate energy usage trends and ensure maximum
uptime. 
Racknet Enabled - The I20004 -- MN02X4W1-36PT68-3PS6B0A10-S easily integrates with
Racknet – Geist’s DCiM software. Racknet (purchased separately) collects and reports
critical power and environmental data for multiple PDUs in one, user configurable interface.
Users gain immediate remote access to trends, alarms and histories of devices in the data
center through a standard Web browser. Racknet saves both time and cost associated
with managing each device individually. Contact your Geist rep for more details.
Product Summary
I20004 -- MN02X4W1-36PT68-3PS6B0A10-S - Upgradeable, Power Unit Level Monitoring,
30A, 208V, Vertical, (30) Locking IEC C13,(6) Locking IEC C19, breakered, 10 ft power cord
with 2P+E, Power – Remote + Current - Local, , Aggregate - Total Unit Monitoring (A, V, W,
VA, kWh, PF) 
Power Measurements Compliant with ANSI C12.1 and IEC 62053-21 1% Accuracy Class
Requirements, Circuit/Breaker Monitoring (A) 
Circuit/Breaker Current Measurements Independently Tested and Verified at 2% Accuracy
Monitoring
Power – Remote + Current - Local
Plug Form
 2P+E
Receptacle
 Locking IEC C13 (Quantity: 30) 
 Locking IEC C19 (Quantity: 6)