SurgeX SA-82 Leaflet

Page of 2
Power Protection + Distribution
Load Rating
Power Requirement (no load)
UL 1449-2 Adjunct Classification Test Results
Federal Guidelines
EMI/RFI Filter, Normal Mode (50-ohm load)
EMI/RFI Filter, Common Mode (50-ohm load)
Maximum Applied Surge Pulse Joule Rating
Maximum Applied Surge Pulse Voltage
Maximum Applied Surge Pulse Current
Endurance
Pulses
Overvoltage Shutdown
Dimensions
Weight
Temperature Range
Humidity Range
Agency Listings
CE
FCC
NETWORK
    
8 Amps @ 120 Volts 
10 Watts 
1000 surges, 6000 volts, 3000 amps,
C1 pulse, measured suppressed voltage 290 volts, 
no failures
Grade A, Class 1, Mode 1 (CID A-A-55818) A
40 dB @ 100 kHz; 50 dB @ 300 kHz; 
50 dB @ 3 MHz; 50 dB @ 30 MHz
18 dB @ 300 kHz; 30 dB @ 1 MHz; 
50 dB @ 5 MHz; 50 dB @ 20 MHz
Unlimited, due to current limiting (8 x 20 µs)* 
6000 Volts* 
Unlimited, due to current limiting* 
IEEE C62.41-1991 Category B3 (C1) 
1 kv>500,000; 3 kv>10,000; 6 kv>1000 
145 Volts (resume at 135 volts) 
1.75" H x 5.31" W x 9.06" D 
3.4 lbs 
5º to 35º C 
5% to 95% R.H., non-condensing 
ETL and cETL certified to (UL 1449;
CSA C22.2 No.8-M1986, R2000)
ETL Certified to UL 1283
8 Amps @ 120 Volts
10 Watts
1000 surges, 6000 Volts, 3000 Amps,
C1 pulse, measured suppressed voltage 290 Volts, 
no failures
40 dB@100 kHz; 50 dB@300 kHz;
50 dB@3 MHz; 50 dB@30 MHz
18 dB@300 kHz; 30 dB@1 MHz;
50 dB@5 MHz; 50 dB@20 MHz
Unlimited, due to current limiting (8 x 20 µs)*
6000 Volts*
Unlimited, due to current limiting* 
IEEE C62.41-1991 Category B3 (C1)
m1 kV>500,000; 3 kV>10,000; 6 kV>1000
145 Volts (resume at 135 Volts)
11.375” W x 7.625” D x 1.8125” H
4.75 lb.
5 - 35° C
5% to 95% R.H., non-condensing
TUV Certified to UL 60950 Listed I.T.E.
File No. E225914
ETL Certified to UL 1449
ETL Certified to 
UL 1283
 
Directives 89/336/EEC, 92/31/EEC and 93/68/EEC
EN 60950
EN55022: 1998 Class B
Part 15 Class B
Single 10/100 Unshielded Twisted Pair Ethernet Jack
IP Addressed: DHCP Assigned or Static
Internal HTTP Web Server
Forms Processing Browser Required
Internal Telnet Server
  
Technical Specifications
FlatPak
TM
*  1.2 x 50 µs pulse, industry standard combination wave surge, as per IEEE C62.41
**  Specifications subject to change without notice. 
This product, including its components and/or processes carried out thereby, are covered by one or more of the following: 
U.S. Pat. No. 4,870,534. 4,870,528. 6,728,089. 6,744,613. 7,068,487. Can. Pat. No. 1,333,191. 1,332,439. Other Patents Pending.
SA-82
SA-82-AR
© 2013 SurgeX / Electronic Systems Protection, Inc.