Enlogic EN1101 Data Sheet

Page of 2
The Critical Component
 
 
 
 
 
      
 
 
 
 
                      
 
LT-50510-A1 
 
 
 
Model: EN1101 
Specifications
 
Electrical
 
Acceptable input voltage 
 
220–240 VAC +6%, -10% 
Input current (phase) 
 
16 A  
Input frequency 
 
50 Hz 
Input power 
 
3.52–3.84 kVA 
Input plug 
IEC-60320 C20 inlet with removable power cord; IEC C19 to 16A, 3-pin 
IEC-60309, type 316P6 
Input phases 
Single input 
Output voltage 
 
220–240 VAC 
Maximum output current (phase) 
 
16 A 
Maximum output current (outlet) 
IEC-320-C13: 10 A 
Outlet Configuration 
(24)C13 
Physical
 
Dimensions (H x W x D) 
106.5 x 5.5 x 4.4 cm 
Weight   
5 Kg 
Shipping dimensions (H x W x D) 
 
119.5 x 17.0 x 11.5 cm 
Shipping Weight  
6.5 Kg 
Power cord length   
3.0 m (removable) 
Environmental
 
Maximum elevation, above MSL (Operating/Storage) 
0–3,000 m / 0–15,000 m 
Temperature (Operating/Storage) 
–5 to 60°C / –25 to 65°C 
Humidity (Operating/Storage) 
 
5–95% RH, non-condensing 
Compliance
 
EMC verification   
EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3 
Safety verification   
TÜV , CE , EN/IEC 60950-1 
Environmental Verification
 
ROHS, WEEE
 
 
 
 
 
 
 
 
 
 
 EN Series Product Data Sheet 
 
EnLogic Systems Europe, Ltd.         EnLogic Systems, LLC.           EnLogic Systems Asia Pacific, Ltd.  
Worcester 
                                Wildwood 
                               Tsim Sha Tsui 
United Kingdom WR1 2PG                          Missouri USA 63040                       Kowloon, Hong Kong 