Enlogic EN1101 Data Sheet
The Critical Component
LT-50510-A1
Model: EN1101
Specifications
Electrical
Acceptable input voltage
220–240 VAC +6%, -10%
Input current (phase)
16 A
Input frequency
50 Hz
Input power
3.52–3.84 kVA
Input plug
IEC-60320 C20 inlet with removable power cord; IEC C19 to 16A, 3-pin
IEC-60309, type 316P6
Input phases
Single input
Output voltage
220–240 VAC
Maximum output current (phase)
16 A
Maximum output current (outlet)
IEC-320-C13: 10 A
Outlet Configuration
(24)C13
Physical
Dimensions (H x W x D)
106.5 x 5.5 x 4.4 cm
Weight
5 Kg
Shipping dimensions (H x W x D)
119.5 x 17.0 x 11.5 cm
Shipping Weight
6.5 Kg
Power cord length
3.0 m (removable)
Environmental
Maximum elevation, above MSL (Operating/Storage)
0–3,000 m / 0–15,000 m
Temperature (Operating/Storage)
–5 to 60°C / –25 to 65°C
Humidity (Operating/Storage)
5–95% RH, non-condensing
Compliance
EMC verification
EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3
Safety verification
TÜV , CE , EN/IEC 60950-1
Environmental Verification
ROHS, WEEE
EN Series Product Data Sheet
EnLogic Systems Europe, Ltd. EnLogic Systems, LLC. EnLogic Systems Asia Pacific, Ltd.
Worcester
Wildwood
Tsim Sha Tsui
United Kingdom WR1 2PG Missouri USA 63040 Kowloon, Hong Kong
sales@emea.enlogic.com
sales@emea.enlogic.com