O n l i n e   U P S
Logix RT Online UPS Selection Guide
MODEL
LOGIX RT 1000
LOGIX RT 1500
LOGIX RT 2000
LOGIX RT 3000
PHASE  
Single phase with ground
CAPACITY
VA
1000 VA
1500 VA
2000 VA
3000 VA 
W
900 W
1350 W
1800 W
2700 W
INPUT
Voltage Range
Low Line Transfer
80 VAC / 70 VAC / 60 VAC / 55 VAC ± 5 % or 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback
85 VAC / 75 VAC / 65 VAC / 60 VAC ± 5 % or 170 VAC / 150 VAC / 130 VAC / 120 VAC ± 5 % 
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
High Line Transfer
150 VAC ± 5 % or 300 VAC ± 5 %
High Line Comeback
140 VAC ± 5 % or 290 VAC ± 5 %
Frequency Range
40Hz ~ 70Hz 
Power Factor
≥ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Output Voltage
110/115/120/127 VAC or 208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
± 1%
Frequency Range (Synchronized Range)
47 ~ 53 Hz or  57 ~ 63 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz
Current Crest Ratio
5:1 (max.)
Harmonic Distortion
≤ 2 % THD (Linear Load) ; ≤ 8 % THD (Non-linear Load)
Transfer Time
Line mode to Battery mode
Zero
Inverter to Bypass
4 ms (Typical)     
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
86% 
88% 
Battery Mode
83% 
85% 
BATTERY
Battery Type
12 V / 9 AH
12 V / 9 AH
12 V / 9 AH
12 V / 9 AH
Numbers
2
3
4
6
Typical Recharge Time
4 hours recover to 90% 
capacity
4 hours recover to 90% 
capacity
4 hours recover to 90% 
capacity
4 hours recover to 90% capacity
Charging Current (max.)
1.0 A
1.0 A
1.0 A
1.0 A
Charging Voltage
27.4 VDC ± 1%
41.1 VDC ± 1%
54.7 VDC ±1%
82.1 VDC ±1%
INDICATORS
LCD Display
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator
ALARM
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continously sounding
PHYSICAL
Dimension, D x W x H (mm)
380 x 438 x 88
 [2U] 
480 x 438 x 88
 [2U] 
480 x 438 x 88
 [2U] 
600 x 438 x 88
 [2U] 
Net Weight (kgs)
12.9
17.6
20.6
28
ENVIRONMENT
Humidity
20-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232 / USB
Supports Windows
2
 
2000/2003/XP/Vista/2008, Windows
2
 
7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
NEXT PARTNUMBERS
LOGIX RT
77111
77112
77113
77114
LOGIX RT EXB (Battery Extension)
77115
77116
77117
77118
NEXT 5+ Warranty Extension (UPS)
11004
11008
11006
11007
NEXT 5+ Warranty Extension (EXB)
11013
11013
11013
11014
SNMP/WEB Interface
99002
99002
99002
99002
Product specifications are subject to change without further notice
Logix RT EXB Battery Pack 
Capacity
1kVA
1.5kVA
2kVA
3kVA
6kVA
10kVA
Battery Type
12 V / 9 Ah
12 V / 9 Ah
12 V / 9 Ah
12 V 9 Ah
12/7Ah
12 V 9 Ah
Battery Number
8 pcs
6 pcs
8 pcs
12 pcs
20 pcs
20 pcs
Dimension 
(DxWxH)
480 x 438 x 88 480 x 438 x 88 480 x 438 x 88 600 x 438 x 88 580 x 438 x 133 580 x 438 x 133
Net Weight (kgs)
31.1
29.1
31.1
43.3
57
63
1kVA/1.5kVA/2kVA/3kVA Battery Pack
6kVA/10kVA Battery Pack
O
nlin