NEXT UPS Systems Logix 1000 77101 Leaflet
Product codes
77101
11
O n l i n e U P S
MODEL
LOGIX 1000
LOGIX 2000
LOGIX 3000
LOGIX 6000
LOGIX 10000
PHASE
Single phase with ground
CAPACITY
1000 VA/800 W
2000 VA/1600 W
3000 VA/2400 W
6000 VA/4800 W
10000 VA /8000 W
INPUT
Voltage
Range
Low Line Transfer
160 VAC ± 5% or 80 VAC ± 5% @ 100% load
110 VAC ± 5% or 50 VAC ± 5% @ 50% load
176 VAC ± 3% @ 100% load
110 VAC ± 3% @ 50% load
Low Line Comeback
175 VAC ± 5% or 85 VAC ± 5% @ 100% load
186 VAC ± 3% @ 100% load
120 VAC ± 3% @ 50% load
High Line Transfer
300 VAC ± 5 % or 150 VAC ± 5 %
300 VAC ± 3%
High Line Comeback
290 VAC ± 5 % or 145 VAC ± 5 %
290 VAC ± 3%
Frequency Range
40 Hz ~ 70 Hz
46 ~ 54 Hz or 56 ~ 64 Hz
Power Factor
≥ 0.99 @ Nominal Voltage (Full load)
≥ 0.99 @ 100% load
OUTPUT
Output Voltage
Output Voltage
208/220/230/240 VAC or 110/115/120/127 VAC
208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
± 3%
± 1%
Frequency Range (Synchronized Range)
47~53 Hz or 57~63 Hz
46 ~ 54 Hz or 56 ~ 64 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1
3:1
Harmonic Distortion
≤ 3 % THD
(Linear Load)
≤ 6 % THD
(Non-linear Load)
≤ 4 % THD (Linear Load)
≤ 7 % THD (Non-linear Load)
≤ 3 % THD (Linear Load)
≤ 6 % THD (Non-linear Load)
Transfer
Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
4 ms (Typical)
Zero
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
85%
88%
89%
Battery Mode
83%
88%
BATTERY
Standard
Model
Battery Type
12 V / 7 Ah
12 V / 7 Ah
12 V / 9 Ah
12 V / 7 Ah
12 V / 9 Ah
Numbers
3
6
6
20
20
Typical Recharge Time
4 hours recover to 90% capacity
7 hours recover to 90%
capacity
9 hours recover to 90%
capacity
Charging Current (max.)
1.0 A
1.0 A
Charging Voltage
41.0 VDC ± 1%
82.1 VDC ±1%
273.0 VDC ±1%
INDICATORS
LCD Display
LCD Display
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
PHYSICAL
Standard
Standard
Model
Dimension,
D
x
W
x
H(mm)
397 x 145 x 220
421 x 190 x 318
592 x 250 x 576
Net Weight (kgs)
13
26
28
81
83
Long-run
Model
Dimension,
Dx W x H
(mm)
397 x 145 x 220
421 x 190 x 318
592 x 250 x 576
Net Weight (kgs)
7
13
13
25
27
ENVIRONMENT
Humidity
Humidity
20-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 45dB@ 1 Meter
Less than 55dB @ 1
Meter
Less than 58dB @ 1
Meter
MANAGEMENT
Smart RS-232
Supports Windows
2
2000/2003/XP/Vista/2008, Windows
2
7, Linux, Unix, and MAC
USB
Optional SNMP
Optional SNMP
Power management from SNMP manager and web browser
NEXT PARTNUMBERS
LOGIX
77101
77102
77103
77104
77105
LOGIX EXB (Battery Extension)
77106
77107
77108
77109
77110
NEXT 5+ Warranty Extension (UPS)
11008
11007
11007
11009
11009
NEXT 5+ Warranty Extension (EXB)
11012
11012
11012
11015
11015
SNMP/WEB Interface
99002
99002
99002
99002
99002
*Derate to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC.
Logix Tower Battery Pack
Capacity (VA)
1000VA
2000VA/3000VA
Battery Type
12 V 7 Ah
12 V 7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah
Battery Number
6pcs
12 pcs
12 pcs
18 pcs
18 pcs
Dimension
(DxWxH) mm
397 X 145 X 220
421 X 190 X 318
535 X 190 X 318
Net Weight (kgs)
18
36
40
55
61
Capacity (VA)
6000VA/10000VA
Battery Type
12 V 7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah
Battery Number
20 pcs
20 pcs
40 pcs
40 pcs
60 pcs
60 pcs
Dimension
(DxWxH) mm
592 X 250 X 576
592 X 250 X 576
830 X 250 X 576
Net Weight (kgs)
64
72
109
125
166
190
* There are several battery options for Logix 2kVA/3kVA/6kVA/10kVA. Please check the
above table for the detailed dimensions.
Logix Online UPS Selection Guide
* 2000VA/3000VA
Battery Pack (capable
for 12 pcs or 18 pcs
batteries inside)
* 6000VA/10000VA Battery
Pack (capable for 20 pcs or
40 pcs or 60 pcs batteries
inside)
* 1000VA Battery Pack
(capable for 6 pcs
batteries inside)
O
nlin
e