NEXT UPS Systems Logix RT EXB 6000 77121 Leaflet

Product codes
77121
Page of 1
13
O n l i n e   U P S
Product specifications are subject to change without further notice
Logix RT EXB Battery Pack 
Capacity
1kVA
1.5kVA
2kVA
3kVA
6kVA
10kVA
Battery Type
12 V / 9 Ah
12 V / 9 Ah
12 V / 9 Ah
12 V 9 Ah
12/7Ah
12 V 9 Ah
Battery Number
8 pcs
6 pcs
8 pcs
12 pcs
20 pcs
20 pcs
Dimension 
(DxWxH)
480 x 438 x 88 480 x 438 x 88 480 x 438 x 88 600 x 438 x 88 580 x 438 x 133 580 x 438 x 133
Net Weight (kgs)
31.1
29.1
31.1
43.3
57
63
1kVA/1.5kVA/2kVA/3kVA Battery Pack
6kVA/10kVA Battery Pack
O
nlin
MODEL
LOGIX RT 6kVA
LOGIX RT 10kVA
PHASE
Single phase with ground
CAPACITY
6000 VA / 5400 W
10000 VA / 9000 W
INPUT
Voltage 
Range
Low Line Transfer
176 VAC @ 100% load
110VAC @ 50% load
Low Line Comeback
186 VAC @ 100% load
120VAC @ 50% load
High Line Transfer
300 VAC
High Line Comeback
290 VAC
Frequency Range
46~54 Hz or 56~64 Hz
Power Factor
≥  0.99  @ 100% load
OUTPUT  
Nominal Voltage
200/208/220/230/240 VAC
AC Voltage Regulation
± 1%
Frequency Range(Synchronized Range)
46~54 Hz or 56~64 Hz
Frequency Range(Batt. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
≤ 2 % THD (Linear Load), ≤ 4 % THD (Non-linear Load)
Transfer 
Time
AC mode to Battery mode 
Zero
Battery mode to AC mode
Zero
Inverter to Bypass
Zero
Bypass to Inverter 
Zero
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
Line Mode
90%
Battery Mode
88%
ECO Mode
96%
BATTERY
Nominal Voltage
240 VDC
Battery Type
12 V / 7 AH
12 V / 9 AH
Numbers
20 (18-20 pcs adjustable)*
20 (18-20 pcs adjustable)*
Charging Current (max.)
1.0 A
1.0 A
Float Charging Voltage
273 VDC (based on battery numbers at 20 pcs)
INDICATORS
LCD Display
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continously sounding
PHYSICAL
Dimension,
 
D x W x H
(mm)
UPS unit: 580 x 438 x 133
 [3U] 
Battery pack: 
580 x 438 x133 
[3U] 
UPS unit: 668 x 438 x 133 
[3U] 
Battery pack: 
580 x 438 x133 
[3U] 
Net Weight (kgs)
UPS unit: 17 
Battery pack: 57
UPS unit: 20
Battery pack: 63
ENVIRONMENT
Operation Humidity
0-95 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 58dBA @ 1 Meter
Less than 60dBA @ 1 Meter
MANAGEMENT
Smart RS-232 / USB
Supports Windows
2
 
2000/2003/XP/Vista/2008, Windows
2
 
7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
NEXT PARTNUMBERS
LOGIX RT
77119
77120
LOGIX RT EXB (Battery Extension)
77121
77122
NEXT 5+ Warranty Extension (UPS)
11010
11010
NEXT 5+ Warranty Extension (EXB)
11016
11016
SNMP/WEB Interface
99002
99002
Logix RT 6KVA/10KVA Online UPS Selection Guide
*When using internal batteries from 18-19, the unit will de-rate according to below formula: P=P
Rating
 x N/20 
** If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.