Panduit RGRB19Y Leaflet
w w w. p a n d u i t . c o m
a p p l i c a t i o n s
StructuredGround
™
Grounding Strips provide
an electrically continuous grounding location
for jumpers. They facilitate easy moves, adds,
and changes, ensuring that UBCs are bonded
without the need for paint scraping or
additional paint piercing hardware. Grounding
for jumpers. They facilitate easy moves, adds,
and changes, ensuring that UBCs are bonded
without the need for paint scraping or
additional paint piercing hardware. Grounding
strips are part of the complete, modular
StructuredGround
StructuredGround
™
Grounding Solution for all
telecommunications bonding needs, from
access floors to pathways and ITE, which
protects ITE and personnel and facilitates data
communications throughout your facility.
access floors to pathways and ITE, which
protects ITE and personnel and facilitates data
communications throughout your facility.
StructuredGround
™
Grounding Strips
Electrostatic Discharge (ESD)
Protection
Protection
Port kit with #12-24 and
M6 thread-forming
screws:
M6 thread-forming
screws:
RGESD2-1
Port kit for
cage nut
mounting rails:
cage nut
mounting rails:
RGESD2B-1
ESD protection
wrist strap:
wrist strap:
RGESDWS
Grounding Busbars
Busbar with #12-24
and M6
thread-forming
screws:
and M6
thread-forming
screws:
RBRB19Y
Busbar for
cage nut
mounting rails:
cage nut
mounting rails:
RGRB19CN
Bonding Conductors
Rack bonding
conductor
(CBN jumper):
conductor
(CBN jumper):
RGCBNJ660P22
Unit bonding
conductor
(equipment
jumper):
conductor
(equipment
jumper):
RGEJ657PFY
Access Floor Grounding Clamps
3/4"-7/8" Round: GPQC07-1/0
1 – 1 1/8" Round,
7/8" Square:
7/8" Square:
GPQC10-1/0
1 1/4" Round: GPQC12-1/0
1 1/2" Round: GPQC15-1/0
1 3/4" Round: GPQC17-1/0
2" Round: GPQC20-1/0
S P E C I F I C A T I O N S H E E T
s p e c i f i c a t i o n s
UL Listed grounding strips shall be installed on a back
equipment mounting rail of each rack and cabinet. The strip
shall be sized to ensure that each Rack Unit (RU) has a
bonding location. Grounding strips shall be bonded to the rail
with paint piercing hardware. Antioxidant shall be applied to the
bonding hardware before installation. The bonding strip shall be
labeled as a grounding location. The Unit Bonding Conductors
(UBC) for each piece of equipment (ITE) shall be bonded
directly to the grounding strip.
equipment mounting rail of each rack and cabinet. The strip
shall be sized to ensure that each Rack Unit (RU) has a
bonding location. Grounding strips shall be bonded to the rail
with paint piercing hardware. Antioxidant shall be applied to the
bonding hardware before installation. The bonding strip shall be
labeled as a grounding location. The Unit Bonding Conductors
(UBC) for each piece of equipment (ITE) shall be bonded
directly to the grounding strip.
k e y f e a t u r e s a n d b e n e f i t s
Patented paint-piercing
components
components
Automatically create the necessary bonds when installed,
saving installation time and costs while preventing errors
saving installation time and costs while preventing errors
Bonds directly to the
equipment mounting rail
equipment mounting rail
Providing a convenient bonding location for ITE which
improves grounding cable management
improves grounding cable management
TIA-607-B and BICSI 002
compliant
compliant
Meets the requirements of commonly referenced
industry standards
industry standards
t e c h n i c a l i n f o r m a t i o n
Performance level:
UL Listed, CSA Certified, RoHS Compliant
Dimensions:
Width = .67" (17mm); Thickness = .05" (1.27mm) for threaded rail
fasteners, .03" (.76mm) for cage nut rail fasteners; Lengths
available to accommodate 42-52 RU
fasteners, .03" (.76mm) for cage nut rail fasteners; Lengths
available to accommodate 42-52 RU
Kit contents:
Grounding strip, antioxidant*, grounding sticker and all appropriate
installation hardware
installation hardware
Part Number
Grounding Strip Length
Individually
Packaged Units
Packaged Units
Carton of Ten Units
Grounding Strip Kits for Threaded Rail Fasteners –
include three each #12-24 x ½" and M6 x 12mm thread-forming screws.
include three each #12-24 x ½" and M6 x 12mm thread-forming screws.
RGS13442-1
RGS13442-10-1
42 RU, 73.40"(1.9m)
RGS134-1Y
RGS134-10-1Y
45 RU, 78.65" (2.0m)
RGS13448-1
RGS13448-10-1
48 RU, 83.90" (2.1m)
RGS13451-1
RGS13451-10-1
51 RU, 89.15" (2.3m)
RGS13452-1
RGS13452-10-1
52 RU, 90.90" (2.3m)
Grounding Strip Kits for Cage Nut Rail Fasteners –
include three cage nut bonding studs, eight bonding nuts and three strip clips.
include three cage nut bonding studs, eight bonding nuts and three strip clips.
RGS134B42-1
RGS134B42-10-1
42 RU, 73.40" (1.9m)
RGS134B-1
RGS134B-10-1
45 RU, 78.70" (2m)
RGS134B48-1
RGS134B48-10-1
48 RU, 83.90" (2.1m)
RGS134B51-1
RGS134B51-10-1
51 RU, 89.15" (2.3m)
RGS134B52-1
RGS134B52-10-1
52 RU, 90.90" (2.3m)
*Cartons of ten units are provided with one package of antioxidant.