Frequency
compatibility
60 Hz
Frequency
compatibility details
Output frequency regulation +/- 0.05Hz (free running)
Output voltage
regulation (line
mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
4 5-15R outlet(s); 8 5-15/20R outlet(s); 2 L6-30R outlet(s); 8 C19 outlet(s)
Output receptacle
details
Total 120V output is limited to 4992 watts for 208V input and 5760 watts for 240V input. Additional 120V capacity is
available with the addition of one SU6000XFMR2U step-down transformer.
Output circuit
breaker
POWER MODULE: Two built-in 30A breakers protect one L6-30R outlet each, Eight built-in 20A breakers protect one
C19 outlet each; TRANSFORMER MODULE: Two 15A breakers protect 2 5-15R outlets each, Two 20A breakers
protect 4 5-15/20R outlets each
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current
(at maximum load)
88.4A (208V), 76.6A (240V)
Nominal Input
Voltage(s) Supported
208V AC; 240V AC
UPS input
connection type
Hardwire
UPS input
connection
description
3 wire single phase input (L1, L2, G)
Recommended
Electrical Service
100A
BATTERY
Full load runtime
(minutes)
5.5 minutes (14,400 watts)
Half load runtime
(minutes)
13.5 minutes (7200 watts)
Expandable battery
runtime
Runtime is expandable with external battery packs
External battery
pack compatibility
Expandable runtime
description
For best results, add external batteries in multiples of two so that both included 8kVA power modules have an equal
number and type of connected battery packs
DC system voltage
(VDC)
240