Panasonic CU-UE12JKE User Manual

Page of 44
19 
Wall
Indoor
Outdoor
15 mm
Sleeve for
tube ass’y
Approx. 5 - 7 mm
Bushing for tube ass’y
Putty or caulking compound
Ø 70 through hole
9.2 Indoor 
Unit 
9.2.1 
How to Fix Installation Plate 
 
 
The centre of installation plate should be at more than 450mm at right and left of the wall. 
The distance from installation plate edge to ceiling should be more than 67mm. 
From installation plate left edge to unit's left side is 62mm (UE9JKE) or 98mm (UE12JKE). 
From installation plate right edge to unit's right is 79mm (UE9JKE) or 112mm (UE12JKE). 
 
B   :
 
For left side piping, piping connection for liquid should be about 10 mm from this line.
 
 
: For left side piping, piping connection for gas should be about 45mm from this line. 
             : For left side piping, piping connecting cable should be about 785mm (UE9JKE) or 800mm (UE12JKE) from 
this line. 
 
1  Mount the installation plate on the wall with 5 screws or more. (If mounting the unit on the wall, consider 
using anchor bolts.) Always mount the installation plate horizontally by aligning the marking-off line with 
the thread and using a level gauge. 
 
2  Drill the piping plate hole with ø70 mm hole-core drill. 
z  Put measuring tape at position as shown in the diagram above. The hole centre is 
obtained by measuring the distance namely 105mm and 145mm for left and right hole 
respectively (UE9JKE), or 150mm and 125mm for (UE12JKE). 
z  Drill the piping plate hole at either the right or left and the hole should be slightly slanted 
to the outdoor side. 
 
9.2.2 
To Drill a Hole in the Wall and Install a Sleeve of Piping 
Insert the piping sleeve to the hole. 
Fix the busing to the sleeve. 
Cut the sleeve until it extrudes about 15mm from the wall  
 
 
 
Finish by sealing the sleeve with putty or caulking compound at the 
final stage.  
 
 
 
 
 
 
 
 
 
 
 
Caution 
When the wall is hollow, please be sure to use the sleeve for tube 
ass’y to prevent dangers caused by mice biting the connecting 
cable.