Panasonic CU-UE12JKE User Manual
32
12.1.6 Low pressure Prevention control (Gas Leakage Detection)
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes.
2. If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
2. If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
Comp Frequency
45 Hz or above
64 Hz or above
58 Hz or above
73 Hz or above
Total Outdoor Current
1b≤1<3 1b≤1<1.6 1b≤1<1.3 1b≤1<1.6
Indoor Piping Temp
20 ℃ or above
25 ℃ or less
20 ℃ or above
25 ℃ or less
Operation Mode
Cool/Dry
Heat
Cool/Dry
Heat
Model UE9JKE
UE12JKE
12.1.7 Low Operation Frequency Protection Control
If all following conditions exists, the compressor will run with the frequency of 40 Hz (UE9JKE, UE12JKE) or 30Hz
(RE15JKE)
(RE15JKE)
Models UE9JKE,
UE12JKE
Intake Air Temp.
≥30 ℃ or <15 ℃
-------------------
Outdoor Temp.
≥38 ℃ or <16 ℃
≥24 ℃ or <4 ℃
Indoor Piping Temp.
<30 ℃
≥0 ℃
Operation Mode
Cool / Dry
Heat
12.1.8 Compressor Tank Temperature Rise Protection Control
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4℃.
Indoor temperature and outdoor temperature is 30±5℃.
Remote Control setting 16℃ and Hi Fan Speed.
Indoor temperature and outdoor temperature is 30±5℃.
Remote Control setting 16℃ and Hi Fan Speed.
• During Heating operations:
Indoor piping temperature - indoor suction is under 5℃.
Indoor temperature and outdoor temperature is 20 ± 2℃.
Remote control setting 30℃ and Hi Fan Speed.
Indoor temperature and outdoor temperature is 20 ± 2℃.
Remote control setting 30℃ and Hi Fan Speed.
b. Control contents
• Compressor stops (and restart after 3 minutes)
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
12.2 Protection Control for Cooling and Soft Dry Operation
12.2.1 Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air temperature.
• Compressor frequency will adjust base on outdoor air temperature.
Outdoor air temp.( ℃.)
38
25
18
11
free
Free
38
26
16
37
22
15
8
Outdoor air temp.( ℃.)