Panasonic CU-UE12JKE User Manual

Page of 44
32 
12.1.6  Low pressure Prevention control (Gas Leakage Detection) 
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes. 
2.  If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off. 
3. This control is not applicable for deice operation. 
 
Comp Frequency 
45 Hz or above
64 Hz or above 
58 Hz or above 
73 Hz or above 
Total Outdoor Current 
1b≤1<3 1b≤1<1.6 1b≤1<1.3 1b≤1<1.6 
Indoor Piping Temp 
20 ℃ or above
25 ℃ or less 
20 ℃ or above 
25 ℃ or less 
Operation Mode 
Cool/Dry 
Heat 
Cool/Dry 
Heat 
Model UE9JKE 
UE12JKE 
12.1.7  Low Operation Frequency Protection Control 
If all following conditions exists, the compressor will run with the frequency of 40 Hz (UE9JKE, UE12JKE) or 30Hz 
(RE15JKE) 
Models UE9JKE, 
UE12JKE 
Intake Air Temp. 
≥30 ℃ or <15 ℃ 
------------------- 
Outdoor Temp. 
≥38 ℃ or <16 ℃ 
≥24 ℃ or <4 ℃ 
Indoor Piping Temp. 
<30 ℃ 
≥0 ℃ 
Operation Mode 
Cool / Dry 
Heat 
12.1.8  Compressor Tank Temperature Rise Protection Control 
a. Control start conditions 
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A. 
• During Cooling and Soft Dry operations: 
Indoor suction temperature - indoor piping temperature is below 4℃. 
Indoor temperature and outdoor temperature is 30±5℃. 
Remote Control setting 16℃ and Hi Fan Speed. 
• During Heating operations: 
Indoor piping temperature - indoor suction is under 5℃. 
Indoor temperature and outdoor temperature is 20 ± 2℃. 
Remote control setting 30℃ and Hi Fan Speed. 
b. Control contents 
• Compressor stops (and restart after 3 minutes) 
• If the conditions above happen 2 times within 20 minutes, the unit will: 
- Stop operation 
- Timer LED blinks and “F91” indicated 
12.2  Protection Control for Cooling and Soft Dry Operation 
12.2.1  Outdoor Air Temperature Control 
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the 
diagram below. 
• This control will begin 1 minute after the compressor starts. 
• Compressor frequency will adjust base on outdoor air temperature. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                                                       
 
Outdoor air temp.( ℃.) 
38 
25 
18 
11 
free 
Free   
38    
26   
16   
37 
22
15
8
Outdoor air temp.( ℃.)