Phoenix Contact Inline terminal IB IL 400 MLR 1-8A 2727365 2727365 Data Sheet

Product codes
2727365
Page of 8
Nov 13, 2013    3 / 8
Technical data
Thermistor input
Number of inputs
2
Inline potentials
Communications power U
L
7.5 V
Current consumption from U
L
max. 45 mA
Segment supply voltage U
S
24 V DC (nominal value)
Current consumption from U
S
max. 160 mA
General
Weight
550 g
Note on weight specifications
Without plug
Mounting type
DIN rail
Protection class
I, IEC 61140, EN 61140, VDE 0140-1
Note
Notes on operation Line protection for the network supply line,
max. 20 A. Observe derating of the POWER-COMBICON
connector
Test section
Supply voltage UL/400 V level 1.2 kV AC 50 Hz 1 min
Test section
Supply voltage US/400 V level 1.2 kV AC 50 Hz 1 min
Test section
Supply voltage US/brake control switch 1.2 kV AC 50 Hz 1 min
Test section
Supply voltage UL/brake control switch 1.2 kV AC 50 Hz 1 min
Test section
Remote bus/400 V level 1.2 kV AC 50 Hz 1 min
Test section
Remote bus/Brake control switch 1.2 kV AC 50 Hz 1 min
Conformance with EMC directives
Test for immunity to interference in acc. with EN 50082-2:1995
Discharge of electrostatic electricity (ESD) EN 61000-4-2:1995/IEC
61000-4-2 6 kV contact discharge, criterion B; 8 kV air discharge,
criterion B
Conformance with EMC directives
Electromagnetic fields EN 61000-4-3:1993/IEC 61000-4-3 Criterion
A; field strength: 3 V/m
Conformance with EMC directives
Fast transients (Burst) EN 61000-4-4:1995/IEC 61000-4-4
Criterion B; Supply lines: 2 kV; Signal/data lines: 2 kV
Conformance with EMC directives
Transient surge voltage (Surge) EN 61000-4-5:1995/IEC
61000-4-5 Criterion B; supply lines DC: 0.5 kV/0.5 kV (symm./
asymm.); criterion B; supply lines AC: 2 kV/4 kV (symm./asymm.)
Conformance with EMC directives
Conducted interference EN 61000-4-6:1993/IEC 61000-4-6
Criterion A; Test voltage 10 V
Noise emission
Test of emitted interference, housing, in acc. with EN
50081-2:1993 EN 55011:1991 class A
Mechanical tests
Vibration resistance in acc. with EN  60068-2-6/IEC  60068-2-6 1g,
evaluation criterion 1
Mechanical tests
Shock in acc. with EN  60068-2-27/IEC  60068-2-27 10 g,
evaluation criterion 1
Diagnostics messages
Overcurrent Error message in the diagnostic code (bus) and
display via the LED ERR on the module
Diagnostics messages
Output stage cannot be controlled Error message in the diagnostic
code (bus) and display via the LED ERR on the module
Diagnostics messages
Module error during self test Message to the master