Janitza UMG 96RM-M 5222039 Data Sheet

Product codes
5222039
Page of 112
112
UMG 96RM-M
Brief instructions
Changing the current transformer setting
Switch to programming mode:
•  Simultaneously press buttons 1 and 2 for approximately 
1 second in order to switch to programming mode. 
The symbols for the programming mode (PRG) and for 
the current transformer (CT) appear. 
•  Confirm the selection with button 1. 
•  The first digit of the input area for the primary current 
starts flashing.
Changing the primary current
•  Change the flashing digit with button 2. 
•  Select the next digit to be changed with button 1. 
The selected digit to be changed starts flashing. 
If the entire number is flashing, the decimal point can 
be moved with button 2.
Changing the secondary current
•  Only 1 A or 5 A can be set as the secondary current. 
•  Select the secondary current with button 1.
•  Change the flashing digit with button 2. 
Leaving the programming mode
•  Simultaneously press buttons 1 and 2 for approx. 
1 second again in order to switch to display mode.
Retrieving measured values
Switch to display mode:
•  If programming mode is still active (the PRG and CT 
symbols appear on the display), simultaneously press 
buttons 1 and 2 for approximately 1 second in order 
to switch to display mode.
•  A measured value display will appear, e.g. for 
the voltage 
Current transformer symbol
(only in programming mode)
Current transformer setting, 
primary current
Display
Programming mode
Current transformer setting, 
secondary current
Button control
•  Pressing button 2 causes 
the measured value displays 
to change from current, 
voltage, power, etc.
•  Pressing button 1 causes 
the mean values, maximum 
values, etc. associated 
with the measured value 
to change.