Entes EPM-06CS-96 Data Sheet

Page of 4
MULTIMETER
EPM-06 / 06C / 06CS
Press SET button for 3 sec.
(trA Fo menu is displayed.)
Find “SP CUr rnt / SP UoL t”
menu by scrolling
UP-DOWN buttons. 
SET
SET
Press SET button, “SP CUr Hý / SP UoL Hý”
menu is displayed.
Press SET button [(CUr Hý L-1/CUr Lo L-1)
/ (UoL Hý L-1/UoL Lo L-1) menu is displayed.]
Press SET button. Blinking the first digit of
displayed value appears.
Press ESC button one by one until “SAU E  SEt  yES” is displayed.
Press SET button. When “SAU E  SEt  yES” is displayed (If you press
ESC button or choose “no” option instead of “yES” then new data will
be cancelled and previous value will be activated).
SET
SET
ESC
SET
Find [(SP CUr Hý/SP CUr Lo) / (SP UoL
Hý/SP UoL Lo)]
 menu by scrolling UP-
DOWN buttons.
Auto Reset Function :
If Auto Reset function is selected as ON;
Each time that the current decreases “50mAxCtr” value,
start-up delay time is reset and when the current value
increases “50mAxCtr”, start-up delay function is
activated.
If Auto Reset function is selected as OFF;
If the power supply is switched off and then switched
on, start-up delay function is activated.
Start-up delay:
Start Delay Time is used to prevent from faulty
switchings  caused by motor start-up current
(demurrage current).
Out1 remain switched ON in this time period (When
U-I is selected); In this time period, even if the current
value exceeds the limits device doesn’t sense it as a
warning. The device doesn’t give a warning even if the
current value isn’t in the setting interval.
This function is used with “Auto Reset” function.
Press SET button. When “SAU E  SEt  yES” is displayed (If you press
ESC button or choose “no” option instead of “yES” then new data will
be cancelled and previous value will be activated).
Find “SP CUr rnt / SP UoL t”
menu by scrolling UP-DOWN buttons.
Press SET button (SP CUr Hý / SP Uol Hý
menu is displayed.)
Press SET button [(CUr ýnS trP on /
AUt o rSt on) / UoL ýnS trP off] is displayed.
Select “on” in order to activating the “instant trip function” (AUt o rSt),
select “off” in order to disactivating the “instant trip function”, by scrolling
UP/DOWN buttons.
Press SET button, [(CUr ýnS trP / AUt o rSt) / UoL ýnS trP] is displayed.
(Selection is entered but is not activated yet. For activating the new
selection, please follow the below steps).
Press ESC button one by one until “SAU E  SEt  yES” is displayed.
SET
SET
SET
SET
ESC
SET
Find [(CUr ýnS trP / AUt o rSt) / UoL ýnS trP]
menu by scrolling UP-DOWN buttons.
Press SET button for  3 sec.
(trA Fo menu is displayed)
In this menu, high set points for voltage values are
programmed. Hý values for Phase-Neutral / Phase-
Phase (according to Star / Delta selection) can be
entered one by one.
Note: High Voltage  values are programmed for
(Phase-Neutral / Phase-Phase) separately but “UoL
Hý HyS” (hysteresis) and “Hý on dEL” (delay on time)
and “Hý oFF dEL” (delay off time) values are common;
these parameters have same values for Phase-Neutral
/ Phase-Phase.
When Connection type (Star/Delta) is selected (refer
to Connection menu), device will change the
UoL Hý L-1, L-2 and L-3 values automatically according
to connection.
If all the voltage values (Phase-Neutral / Phase-Phase)
are under the Hý value; releated relay is switched on,
its LED turned on (please refer “Output”) and releated
H LEDs are turned off.
If all the voltage values (Phase-Neutral / Phase-Phase)
are over the Hý value, H LED blinks and releated output
is switched off at the end of “delay on time”
(Hý on dEL), its LED turned off (please refer “Output”)
and releated H LEDs are turned on.
If all voltage (Phase-Neutral / Phase-Phase) are below
the high set value (Hi) as a hysteresis voltage (UoL Hý
HyS), releated output is switched on at the end of the
“delay off time” (Hý oFF dEL), its LED turned on (please
refer “Output”) and H LED is turned off.
Programming “SP UoL t” :
Using purposes of submenus of “SP UoL t” explained below with
details.
Example : If the connection type is selected as Star
(with neutral); UoL Hý HyS=10V UoL Hý L-1=250V,
UoL Hý L-2=255V, UoL Hý L-3=260V
and then this connection type is selected as Delta
(without neutral), device will change the values after
calculated them according to Phase-Phase values.
New values;
UoL Hý L-1 (L1-L2 Phase to phase voltage) = 433 V
UoL Hý L-2 (L2-L3 Phase to phase voltage) = 441 V
UoL Hý L-3 (L3-L1 Phase to phase voltage) = 450 V
UoL Hý HyS = 10 V.
T h e r e   a r e   6   s u b m e n u s .
U oL Hý  L - 1 ,   U o L   H ý   L - 2 ,   U o L   H ý   L - 3 ,   U o L   H ý
H y S ,   H ý   o n   d E L ,   H ý   o F F   d E L .
4
Programming “CUr ýnS trP”, “AUt o rSt” and “UoL ýnS trP”
Programming the “SP CUr Hý”, “SP CUr Lo”, “SP UoL Hý” and “SP UoL Lo”.
Enter the blinking digit
value by scrolling
UP/DOWN buttons.
Switch to the other digits
by using SET button, use
ESC button to go to previous digit. After you entered the last digit
press SET button, “CUr Hý L-1/CUr Lo L-1) / (UoL Hý L-1/UoL Lo L-1”
is displayed. (Data is entered but is not activated yet. For activating
the new data please follow the below steps).
SET
Instant Tripping Function.
At position ON, if any phase current (IL1, IL2, IL3 and
IN) exceeds 1.5 times of high (CUr Hý L-1, L-2, L-3,
L-n) values, the “current output” switches off instantly,
output LED turned off and H LEDs for related currents
turned on. (Please refer to “Output”.)
At position OFF, if any phase current (IL1, IL2, IL3 and
IN) decrease 0.5 times of low (CUr Lo L-1, L-2, L-3,
L-n) values, the “current output” switches off instantly,
output LED turned off and L LEDs for related currents
turned on. (Please refer to “Output”.)
At position OFF, instant tripping function is cancelled.
MULTIMETER
EPM-06 / 06C / 06CS
Low value for L1, when the Star is
selected; low value for L1-L2, when the
Delta selected can be defined in this
menu.
0....300 for Star connection and
0....500 for Delta connection can be
defined.
If the value is set to zero (0), the high
voltage warning is disabled. Refer “SP
Uol Lo” for details.
Note: L2 and L3 phases can be
programmed similarly.
(Refer to Page-4 for SP CUr Hý, SP CUr Lo,
SP UoL Hý ve SP UoL Lo
)
When Connection type (Star/Delta) is selected (refer
to Connection menu), device will change the
UoL Lo L-1, L-2 and L-3 values automatically according
to connection.
In this menu, low set points for voltage values are
programmed. Lo values for Phase-Neutral / Phase-
Phase (according to Star / Delta selection) can be
entered one by one.
Example : If the connetion type is selected as Star
(with neutral); UoL Lo Hys=10V
UoL Lo L-1=180V, UoL Lo L-2=175V, UoL Lo L-3=170V
and then this connection type is selected as Delta
(without neutral), device will change the values after
calculated them according to Phase-Phase values.
New values;
UoL Lo L-1 (L1-L2 Phase to phase voltage) = 311 V
UoL Lo L-2 (L2-L3 Phase to phase voltage) = 303 V
UoL Lo L-3 (L3-L1 Phase to phase voltage) = 294 V
UoL Lo HyS = 10 V.
If all the voltage values (Phase-Neutral / Phase-Phase)
are over the Lo value; releated output is switched on,
its LED turned on (please refer “Output”) and releated
L LEDs are turned off.
If any of the voltage valueses (Phase-Neutral / Phase-
Phase) decrease the Lo value, L LED blinks and
releated output is switched off at the end of “delay
on time” (Lo on dEL), its LED turned off (please refer
“Output”) and releated L LED is turned on continuously.
If all voltage (Phase-Neutral / Phase-Phase) values
increase the low set value (Lo) as a hysteresis voltage
(UoL Lo HyS), releated relay is switched on at the end
of the “delay off time” (Lo oFF dEL), its LED turned on
(please refer “Output”) and L LED is turned off.
Note: Low Voltage  values are programmed for (Phase-
Neutral / Phase-Phase) separately but “UoL Lo HyS”
(hysteresis), “Lo on dEL” (delay on time) and “Lo oFF
dEL” (delay off time) values are common; these
parameters have same values for Phase-Neutral /
Phase-Phase.
High value for L1, when the Star is
selected; high value for L1-L2, when the
Delta selected can be defined in this
menu.
0....300 for Star connection and
0....500 for Delta connection can be
defined.
If the value is set to zero (0), the high
voltage warning is disabled. Refer “SP
Uol Hý” for details.
Note: L2 and L3 phases can be
programmed similarly.
In this menu, required hysteresis voltage
for high voltage warning is programmed.
(same for Phase-Neutral/Phase-Phase.)
0....200V for Star connection and
0....200V for Delta connection can
be defined.
Refer “SP UoL Hý” for details.
In this menu, required hysteresis voltage
for low voltage warning is programmed.
(same for Phase-Neutral/Phase-Phase.)
0....200V for Star connection and
0....200V for Delta connection can
be defined.
Refer “SP UoL Lo” for details.
Press SET button for 3 sec.
(trA Fo menu is displayed.)
SET
SET
Press SET button (SP UoL Hý / SP CUr Hý
menu is displayed.)
Press SET button [(Uo L   H ý  L-1/UoL Lo L-1)
/ (CUr Hý L-1/CUr Lo L-1) menu is displayed.]
Press SET button. Blinking the first digit of
displayed value appears.
Press ESC button one by
one until “SAU E  SEt  yES”
is displayed.
SET
SET
ESC
SET
Find [(SP UoL Hý / SP UoL Lo) / (SP CUr Hý
/ SP CUr Lo)] 
menu by scrolling
UP-DOWN buttons
Find [(UoL Hý HyS / UoL Lo HyS) / (CUr Hý HyS / CUr Lo HyS)] menu
by scrolling UP-DOWN buttons.
“Delay on” time for activating the output for
high voltage warning. It is common for all
voltages (same for Phase-Neutral/Phase-
Phase.)
The  value can be programmed between
000,0 and 999,9 in terms of seconds.
(Refer “SP UoL Hý” for details.)
“Delay on” time for activating the output for
low voltage warning. It is common for all
voltages (same for Phase-Neutral/Phase-
Phase.)
The  value can be programmed between
000,0 and 999,9 in terms of seconds.
(Refer “SP UoL Lo” for details.)
“Delay off” time for activating the output for
high voltage warning. It is common for all
voltages (same for Phase-Neutral/Phase-
Phase.)
The  value can be programmed between
000,0 and 999,9 in terms of seconds.
(Refer “SP UoL Hý” for details.)
“Delay off” time for activating the output for
low voltage warning. It is common for all
voltages (same for Phase-Neutral/Phase-
Phase.)
The  value can be programmed between
000,0 and 999,9 in terms of seconds.
(Refer “SP UoL Lo” for details.)
5
Programming the “U-H HyS”, “U-L HyS”, “I-H HyS”, “I-L HyS”
Press SET button for 3 sec.
(trA Fo menu is displayed.)
SET
SET
Press SET button (SP UoL Hý / SP CUr Hý
menu is displayed.)
Press SET button [(UoL Hý L-1 / UoL Lo L-1)
/(CUr Hý L-1 / CUr Lo L-1) menu is displayed.]
SET
Find [(SP UoL Hý / SP UoL Lo) / (SP CUr Hý
/ SP CUr Lo)] 
menu by scrolling
UP-DOWN buttons.
Find [(Hý on dEL / Hý oFF dEL / Lo on dEL / Lo oFF dEL) / (Hý on dEL /
Hý oFF dEL / Lo on dEL / Lo oFF dEL)] 
menu by scrolling UP-DOWN
buttons.
“Hý on dEL”, “Hý oFF dEL”, “Lo on dEL”, “Lo oFF dEL” settings are
explained for SP UoL t and SP CUr rnt
Enter the blinking digit value by
scrolling UP/DOWN buttons.
Switch to the other digits by using
SET button, use ESC button to go to
previous digit. After you entered the last
digit press SET button,
[(UoL Hý HyS / UoL Lo HyS) / (CUr Hý HyS / CUr Lo HyS)]
 is displayed.
(Data is entered but is not activated yet. For activating the new data
please follow the below steps).
SET
Please refer to below graphics for the operating
principle of StA rt dEL and Aut o rSt  functions
T h e r e   a r e   6   s u b m e n u s .
U oL Lo  L - 1 ,   U o L   L o   L - 2 ,   U o L   L o   L - 3 ,   U o L
L o   H y S , L o   o n   d E L ,   L o   o F F   d E L .
Find “SP UoL t / SP CUr”
menu by scrolling
UP-DOWN buttons.
Press SET button. When
“SAU E  SEt  yES” is
displayed (If you press ESC button or choose “no” option instead of “yES”
then new data will be cancelled and previous value will be activated).
Find “SP UoL t / SP CUr”
menu by scrolling
UP-DOWN buttons.
5 A
4 A
3 A
2 A
1 A
Un (on)
Un (off)
I L1
Switch-on
Switch-off
Switch-on
Switch-off
Out1
Out2
Auto
on
Auto
of
Out1
Out2
Switch-on
Switch-off
Switch-on
Switch-off
Hý on dEL =  10 sec.
Lo on dEL
=  10 sec.
Hý oFF dEL =  5 sec.
Lo oFF dEL =  5 sec.
Start
=  15 sec.
CUr Hý L1
=  3A
CUr Lo L1  =  1A
Ins. trp 
=  on
Start
Start
Start
t(s)
Start
Start
Start
Hý on
dEL
Hý on
dEL
Hý oFF
dEL
Hý on
dEL
t(s)
t(s)
t(s)
t(s)
t(s)
Hý on
dEL
Hý oFF
dEL
Lo oFF
dEL
Ins.
trp.
Lo oFF
dEL
Ins.
trp.
Lo on
dEL
Lo oFF
dEL
Lo on
dEL
Lo oFF
dEL
10
20
30
40
50
60
70
80
90
100 110
120 130
140
150 160
170
180
190
200
Hý on
dEL
Hý oFF
dEL