E35.0.01.6C-03                     Manual for connection and operation of the EB 3000                          page 6 of 19
4. Electric connection
Electric connection and commissioning of the device must be carried out by trained and skilled personnel.
Wrong connection may lead to the destruction of the device, in which case we cannot assume any
warranty.
Make it a rule to always mount screw-type/plug-in terminals while they are still loose and connect only later. If terminals
are mounted after connection there is a risk that soldering eyes may come loose. Please use suitable screw-driver and
do not tighten screws by force.
4.1. Terminal assignment
14 Switching output 1..4 (common connector)
13 Switching output 1  (normally open)
12 Switching output 2  (normally open)
11 Switching output 3  (normally open)
10 Switching output 4  (normally open)
9
Alarm output (normally closed)
8
Alarm output (normally open)
7
Alarm output (common connector)
6
Supply voltage: 230V
AC
5
Supply voltage: 230V
AC
4
EASY
BUS
-Input
(to PC/Host)
3
EASY
BUS
-Input
(to PC/Host)
2
EASY
BUS
-Output
(to 
EASYBUS-sensor modules)
1
EASY
BUS
-Output
(to 
EASYBUS-sensor modules)
4.2. Connection data
typical
limitations
between
terminal
min.
max.
min.
max.
notes
Supply voltage
5 and 6
207
 
V
AC
243
 
V
AC
250
 
V
AC
or as specified on rating plate
Switching outputs
14 and 13,
14 and 12,
14 and 11,
14 and 10
250
 
V
AC
5A
(ohmic load)
Use RC circuit elements or
varistors for inductive loads
Alarm output
7 and 8, 9
250
 
V
AC
5A
(ohmic load)
Use RC circuit elements or
varistors for inductive loads
EASY
BUS
-output
1 and 2
36
 
V
DC
EASY
BUS
-input
3 and 4
36
 
V
DC
These limits must not be exceeded (not even for a short time) !