E33.0.31.6C-02     Manual for connection and operation of the GIR230 Pt1000 / DIF and GIR230 NTC /DIF        Page 10 of 14
5.3. Minimum/maximum-alarm
This chapter describes how to configure the device‘s alarm boundaries for min-/max-alarm-monitoring.
This instruction demands that you selected “AL“ as your desired output function.
- Press button 1 
(when not already done)
 , the device will be displaying “AL.Hi“. (maximum alarm-value)
- Use button 2 and button 3 to set the desired value, the device should turn on its maximum-alarm.
- Press button 1 to validate your selection. The display shows “AL.Hi“ again.
- When pressing button 1 again, the device will be displaying “AL.Lo“. (minimum alarm-value)
- Use button 2 and button 3 to set the desired value, the device should turn on its minimum-alarm
- Press button 1 to validate your selection. The display shows “AL.Lo“ again.
- When pressing button 1 again, the device will be displaying “A.dEL“. (delay of the alarm-function)
- Use button 2 and button 3 to set the desired delay of the alarm-function.
  Note: The unit of the value to be set [0 .. 9999] is in seconds. The device will turn on the alarm after
minimum or maximum alarm value was active for the delay-time you have set.
- Press button 1 to validate the delay time. The display shows “A.dEL“ again.
Example: You want to have a temperature alarm-monitoring of a greenhouse. The alarm should start when
the temperature rises above 50°C or falls below 15°C. Therefore your settings will be 50°C for the
maximum alarm-value “AL.HI“ and 15°C for the minimum alarm-value “AL.Lo“.
The alarm will be starting after the temperature rises above 50°C and stays above 50°C for the
entered delay time or after it had been falling below 15°C and stays below 15°C for the entered
delay time.
Please note that the alarm-outputs are inverted! This means, that the output will be active when there is no alarm!
Now you finished configuring your device. Press button 1 to switch over to display the measuring value.
6. Min-/Max-alarm display
If a output function with alarm (out = 2P.AL, 3P.AL or AL) is selected and there is an alarm condition the display
alternates between measuring value and AL.Lo or AL.Hi
Min.-alarm:
approx. all 2 sec. AL.Lo will be shown in the display
Max.-alarm: 
approx. all 2 sec. AL.Lo will be shown in the display
7. Displaying the measuring value of input 1 or input 2
The display will normally show the difference value (input 1 – input 2).
Also the measuring value of input 1 and input 2 can be called for a short time.
Calling of meas. value input 1: press button 1 shortly
the device will display“INP.1“ briefly, after that the
meas. value of input 1 is displayed for about 2 sec.
Calling of meas. value input 2: press button 1 shortly 2-times the device will display“INP.2“ briefly, after that the
meas. value of input 2 is displayed for about 2 sec.
8. Min-/max-value storage
The device features a minimum/maximum-value storage. In this storage the highest and lowest measured value
are saved.
Calling of the minimum-value
press button 3 shortly
the device will display “Lo“ briefly, after that
the min-value is displayed for about 2 sec.
Calling of the maximum-value press button 2 shortly
the device will display “Hi“ briefly, after that
the max-value is displayed for about 2 sec.
Erasing of the min/max values press button 2 and 3 for 2 sec.
The device will display “CLr“ briefly, after
that the min/max-values are set to the cur-
rent displayed value.