Weigel Mains-analysis device, Mains analyser 6790006 Data Sheet

Product codes
6790006
Page of 4
Data Sheet
679.D.121.04
Digital Multifunctional
Power Meter
with LCD Display
4 Quadrants Measurement
0
0
+1
-1
capacitive
motor/
import
inductive
motor/
import
capacitive
generator/
export
inductive
generator/
export
Reactive energy
+90°
-90°
Active energy
ϕ
±180°
cos 
ϕ
Q1
Q2
Q3
Q4
Environmental
operating temperature –20 ... +60
°C
range
storage temperature
–30 ... +70
°C
range
relative humidity
5% ... 95% non-condensing
Status Inputs
WPM 735 E is equipped with 8 status inputs which can be used, e.g. for
recording switch positions.
internal supply
30 V DC
Pulse Outputs
WPM 735 E is equipped with two pulse outputs:
D Output P1 provides pulses for total active energy.
D Output P2 provides pulses for total reactive energy.
supply+
to receptor
supply –
WPM 735 E
external devices
type
optocoupler open–collector, max. 50 V, 50 mA
pulse weight
adjustable 1000 ... 5000, 
depending on CT ratio, 
i.e. with 1 kWh/kvarh X CT
the set pulse count will be output
pulse width
max. 200 ms
Analog Output
WPM 735 E is equipped with one analog output, to which a measured
rating can be assigned.
type
4 ... 20 mA
burdan range
0 ... 500 
W
scale factor
1 ... 10 adjustable
RS485 Interface
type
RS485
protocol
MODBUS–RTU
baud rate
2400, 4800, 9600, 19200
address
1 ... 247
example
WPM 735
WPM 735
WPM 735
Standards
EN 55022
Information technology equipment – 
Radio disturbance characteristics – 
Limits and methods of measurement
EN 55024
Information technology equipment – 
Immunity characteristics – 
Limits and methods of measurement
EN 60950–1
Information technology equipment – Safety – 
Part 1: General requirements
EN  61000–3
Electromagnetic compatibility (EMC) – Limits –
–2
Part 3–2: Limits for harmonic current emissions
(equipment input current <= 16 A per phase)
–3
Part 3–3: Limitation of voltage changes, 
voltage fluctuations and flicker in public 
low–voltage supply systems, for equipment 
with rated current <= 16 A per phase and 
not subject to conditional connection
IEC 61000–4
Electromagnetic compatibility (EMC) – 
Testing and measurement techniques –
–2
Part 4–2: Electrostatic discharge 
immunity test.
–3
Part 4–3: Radiated, radio–frequency, 
electromagnetic field immunity test
–4
Part 4–4: Electrical fast transient/burst 
immunity test
–5
Part 4–5: Surge immunity test
–6
Part 4–6: Immunity to conducted disturbances, 
induced by radio–frequency fields
–8
Part 4–8: Power frequency magnetic field 
immunity test
–11
Part 4–11: Voltage dips, short interruptions 
and voltage variations immunity tests