Fluke Fluke 4325162 User Manual

Product codes
4325162
Page of 56
 
Earth/Ground Tester 
 
Advanced Operation 
31 
Compensation of Earth Electrode Connecting Lead 
If the line resistance to the earth electrode cannot be ignored, a compensation of the 
connecting lead resistance to the earth electrode is possible.  
Measuring process: 
Auxiliary 
earth
electrode
Earth
electrode
 
edw019.eps 
Figure 10. Compensation of Earth Electrode Connecting Lead 
To do a compensation: 
1.  Turn central rotary switch to position "R
E
 3pole".  
2.  Wire instrument as shown in Figure 10. 
3.  Call display R
K
 with "DISPLAY MENU" button. 
4.  Implement compensation with "START TEST" button. 
The compensation resistance is displayed only for as long as the "START TEST" button 
is kept pressed. After releasing the "START TEST" button the measured value is stored 
and the measuring instrument returns to the standard settings at the beginning of the 
measurement so that a succeeding measurement of the earthing resistance can be 
implemented by pressing "START TEST" again. Thereafter, R
K
 is subtracted from the 
actual measured value. 
If the compensation value has to be reset to the basic setting (0.000 
Ω
), the 
compensation sequence has to be implemented with an open (disconnected) measuring 
lead or turn the switch to the next position and back.