Fluke Fluke 4325181 User Manual

Product codes
4325181
Page of 56
 
Earth/Ground Tester 
 
Features 
Features 
The 1625-2 Earth/Ground Tester (Tester) is an earth resistance meter with fully 
automated measuring frequency selection process. The Tester includes automatic testing 
of probe and auxiliary earth electrode resistances and possible interference voltages in 
accordance with DIN IEC61557-5/EN61557-5: 
  Measurement of interference voltage (U
ST
  Measurement of interference frequency (F
ST
  Measurement of probe resistance (R
S
  Measurement of auxiliary earth electrode resistance (R
H
  Measurement of earthing resistance 3-pole, 4-pole, (R
E
) with or without using the 
external clip-on current transformer for selective measurement of single earthing 
branches in mesh operated earthing systems  
  Resistance measurement 2-pole with ac voltage (R~) 
  Resistance measurement with dc voltage 2-pole, 4-pole, (R) 
With its various possibilities of measurement and the fully automated measuring 
sequence control (incl. automatic frequency control AFC), this instrument offers the latest 
measuring technology in the field of earthing resistance measurements. By means of the 
selectable limit input with visual and acoustical confirmation/error message and with the 
code programmable and customer defined special functions, such as measuring voltage 
20 V (for agricultural systems), earthing impedance R* (measuring frequency 55 Hz) 
switched on or off, these instruments are individually programmable for use as a simple 
meter as well as a high end fully automated measuring device. 
The Tester includes automatic testing of probe, auxiliary earth electrode resistances, and 
possible interference voltages. 
See Table 3 for a list of features and functions. 
 Warning  
 
No voltage permissible to sockets 
 
Do not open or close the instrument with force. 
 
Disconnect all leads before opening the instrument.