Fluke Fluke 4325181 User Manual

Product codes
4325181
Page of 56
 
Earth/Ground Tester 
 
Setup 
15 
Description of Functions 
The functions are selected with the central rotary switch. Four push buttons start 
measurements, read out supplementary measurement values, and select special 
functions. See Table 6 for more information. 
Measurement values are shown on a liquid crystal display with units. Additional special 
characters indicate measurement mode, operating condition and error messages. 
The Tester includes these measurement functions: 
  Interference Voltage (U
ST
Fullwave rectification for dc and ac. If limit values are 
exceeded no measurement will be started. 
  Interference Frequency (F
ST
For interference voltage >1 V its frequency is derived 
from the period time. 
  Earthing Resistance (R
E
The earthing resistance is determined by a 3-pole or 
4-pole current and voltage measurement. The 
measuring voltage is a square pulse ac voltage with 48 / 
20 V and a frequency of 94, 105, 111 or 128 Hz. The 
frequency can be selected manually or automatically 
(AFC). 55 Hz in function R*. 
  Selective Measurement of 
Earthing (R
E
 
Measurement of a single earth electrode in a mesh 
operated (parallel) earthing system. The current flowing 
through the single earth electrode is measured with an 
external current transformer. 
  Resistance (R~) 
The resistance is determined by a 2-pole current and 
voltage measurement. The measuring voltage is a 
square pulse ac voltage with 20 V and a frequency of 
94, 105, 111 or 128 Hz. The frequency can be selected 
manually or automatically (AFC).  
  Low Resistance (R
The resistance is determined by dc current and voltage 
measurement. 2-pole as well as 4-pole measurement is 
possible. The short circuit current is > 200 mA. The 
resistance of both current directions is measured and 
stored. 
  Checking for Correct 
Measurement Connection 
The Tester checks if the measuring lead is properly 
connected according to the selected function via 
isolated, two piece contacts, inside of each 4 mm 
(banana) input socket, in combination with detection 
circuitry. A wrong or missing connection is indicated by 
an optical and acoustical signal. 
  Beeper 
The built-in beeper has two functions: 
  Send message if set limit values are exceeded. 
  Indicates dangerous condition or faulty operation. 
  Battery Level Indicator 
A 4-segment battery level indicator shows the battery 
status.