Earth/Ground Tester 
 
Advanced Operation 
21 
3-Pole/4-Pole Measurement of Earthing Resistance 
This measuring function measures earthing and earth dissipation resistances of single 
earth electrodes, foundation earth electrodes and other earthing systems by using two 
earth spikes. See Figure 4. 
4 Pole
Auxiliary 
earth
electrode
Probe
Earth
electrode
>20 m
>20 m
 
edw012.eps 
Figure 4. 3-Pole/4-Pole Measurement of Earthing Resistance - Process 
1.  Turn central rotary switch to position "R
E
 3pole" or "R
E
 4pole"  
The instrument is to be wired according to picture and notices given on the display. 
A flashing of the sockets symbols  or , points to an incorrect or 
incomplete connection of the measuring lead. 
2.  Press "START TEST" button.  
Now a fully automated test sequence of all relevant parameters like auxiliary earth 
electrode and probe and earth electrode resistance is implemented and finished with 
the display of the result R
E
.  
3.  Read out measured value R
E
.  
4. Call 
R
S
 and R
H
 with "DISPLAY MENU".