Operation 
11 
Operation 
The Tester is equipped with a 3-pole as well as a 4-pole resistance measurement that 
renders measurements of resistances of earthing systems and measurements of the soil 
resistivity of geological strata. The Tester also makes measurements with an external 
current transformer, with which a measurement of single resistance branches in 
interlinked networks (lightning protection and high voltage pylons with cabling) can be 
performed without separating parts of the system. 
R
A
 2-Pole, 3-Pole Measurements 
To make 2-pole or dead-earth measurements, connect a jumper between terminals H/C2 
and S/P2 with the supplied connector cable. Use only the earth electrode and the 
auxiliary earth electrode. Minimum distance between earth electrode (E/CD1) and 
auxiliary earth (H/C2) should be at least 20 m. 
See Figures 3 and 4 and do steps 1 thru 4: 
1. Select 
3 POLE
2.  Connect the test leads. 
Connect terminal E/C1 to the earth/ground system to be measured with the 
supplied test lead and clip (1.5 m). Place two ground stakes in earth/dirt.  
Note 
Minimum distance between earth electrode (E/C1), probe 
(S/P2), and auxiliary earth (H/C2) should be at least 20 m. 
Connect the stakes with the 25 m and 50 m cable reels to H/C2 and S/P2 as 
shown in Figures 3 and 4. 
3. 
 
Push START
 indicates that a measurement is in progress. For a continuous 
measurement, continue to push the START button. 
4.   indicates a completed measurement. The result is kept on the display until a 
new measurement is started or the main switch is turned.