Earth/Ground Tester 
 
Operation 
15 
R
A
 3-Pole Selective Earth Resistance Measurement with Current Clamp 
The R
A
 3-pole Selective Earth Resistance Measurement with Current Clamp procedure is 
useful for the resistance measurement of different parallel sections of an earth/ground 
system.  
1.  Select 3 POLE . See Figure 6. 
2.  Connect test leads.  
Connect the supplied test lead (1.5 m) to terminal E/C1 and its other end to the 
ground system to be measured. Place two ground stakes in earth/dirt. Minimum 
distance between earth electrode (E/C1), probe (S/P2) and auxiliary earth (H/C2) 
should be at least 20 m. 
Connect stakes with 25 m and 50 m wires to H/C2 and S/P2 as shown. 
Connect current clamp with adapter cable as shown. 
3.  Push START
 indicates that measurement is in progress. For continuous 
measurement, continue to push the START button. 
4.   indicates completed measurement. The result is kept on display until a new 
measurement is started or the rotary switch is turned.