Ht Instruments COMBI G2VDE-tester 1009990 Data Sheet

Product codes
1009990
Page of 6
 
 
      
COMBIG2
 
Rel 1.00  of 27/08/14
 
Professional installation safety tester 
Pag 1 of 6
 
 
HT ITALIA SRL 
Via della Boaria 40 - 48018 Faenza (RA)- Italy 
Tel: +39-0546-621002  - Fax: +39-0546-621144 
email: export@htitalia.it  -  web: http://www.ht-instruments.com 
 
1. ELECTRICAL SPECIFICATIONS
 
Accuracy is indicated as 
 ( readings + no. of digits*resolution) at 23°C  5°C, <80HR 
 
Voltage (RCD, LOOP, Phase sequence) 
Range [V] 
Resolution [V] 
Accuracy 
15 
 460 
(3.0 rdg + 2dgt) 
 
Frequency 
Range [Hz] 
Resolution [Hz] 
Accuracy 
47.0 
 63.6 
0.1 
(0.1 rdg + 1dgt) 
 
Continuity test on protective and equalizing conductors 
Range [
Resolution [
Accuracy (*) 
0.01 
 19.99 
0.01 
(5.0rdg + 3dgt) 
20.0 
 99.9 
0.1 
(*) calibrate the cables to null their resistance 
Test current: 
> 200mA DC for R
5 (calibration included) ; Resolution for DC current :1mA 
Open-circuit voltage: 
 
4V 
 V
0
 
 12V 
Insulation resistance (DC voltage) 
Test voltage[V] 
Range [M
Resolution [M
Accuracy 
50 
0.01 
 9.99 
0.01 
(2.0rdg + 2dgt) 
10.0 
 49.9 
0.1 
50.0 
 99.9 
0.1 
(5.0rdg + 2dgt) 
100 
0.01 
 9.99 
0.01 
(2.0rdg + 2dgt) 
10.0 
 99.9 
0.1 
100.0 
 199.9 
0.1 
(5.0rdg + 2dgt) 
250 
0.01 
 9.99 
0.01 
(2.0rdg + 2dgt) 
10.0 
 99.9 
0.1 
100 
 499 
(5.0rdg + 2dgt) 
500 
0.01 
 9.99 
0.01 
(2.0rdg + 2dgt) 
10.0 
 199.9 
0.1 
200 
 499 
500 
 999 
(5.0rdg + 2dgt) 
1000 
0.01 
 9.99 
0.01 
(2.0rdg + 2dgt) 
10.0 
 199.9 
0.1 
200 
 999 
1000 
 1999 
(5.0rdg + 2dgt) 
Open-circuit voltage: 
nominal test voltage  –0% +10% 
Short circuit current: 
<6.0mA at 500V test voltage 
Nominal test current: 
>1mA if load= 1k
*Vnom  (Vnom=50V, 100V, 250V, 500V, 1000V) 
Safety protection: 
the display shows an error message for input voltage >10V 
 
Z Line (Line-Line, Line-Neutral, Line-PE) 
Range [
Resolution [
Accuracy 
0.00 
 199.9
 m
 (*)
 
0.1
 m
 (*)
 
(5.0 rdg + 1
m
)
 (*)
 
200 
 1999 
m
 (*)
 
1
 m
 (*)
 
0.01 
 9.99
 
 
0.01
 
 
(5.0 rdg + 3dgt) 
10.0 
 199.9
 
 
0.1
 
 
(*) By means of IMP57 optional accessory 
Maximum test current: 
5.81A (at 265V); 10.10A (at 457V) 
Test voltage ranges: 
100
265V (Line-Neutral) / 100460V (Line-Line); 50/60Hz  5% 
Protection type: 
MCB (B, C, D, K), Fuse (gG, aM) 
Insulation materials: 
PVC, Rubber butyl, EPR, XLPE 
 
First fault current (IT systems) 
Range (mA) 
Resolution (mA) 
Accuracy 
0.1 
 0.9 
0.1 
(5.0 rdg + 1dgt) 
 999 
(5.0 rdg + 3dgt)
 
Limit contact voltage (ULIM) : 
25V, 50V