Ht Instruments COMBI G2VDE-tester 1009990 Data Sheet
Product codes
1009990
COMBIG2
Rel 1.00 of 27/08/14
Professional installation safety tester
Pag 1 of 6
HT ITALIA SRL
Via della Boaria 40 - 48018 Faenza (RA)- Italy
Via della Boaria 40 - 48018 Faenza (RA)- Italy
Tel: +39-0546-621002 - Fax: +39-0546-621144
email: export@htitalia.it - web: http://www.ht-instruments.com
email: export@htitalia.it - web: http://www.ht-instruments.com
1. ELECTRICAL SPECIFICATIONS
Accuracy is indicated as
( readings + no. of digits*resolution) at 23°C 5°C, <80HR
Voltage (RCD, LOOP, Phase sequence)
Range [V]
Resolution [V]
Accuracy
15
460
1
(3.0 rdg + 2dgt)
Frequency
Range [Hz]
Resolution [Hz]
Accuracy
47.0
63.6
0.1
(0.1 rdg + 1dgt)
Continuity test on protective and equalizing conductors
Range [
]
Resolution [
]
Accuracy (*)
0.01
19.99
0.01
(5.0rdg + 3dgt)
20.0
99.9
0.1
(*) calibrate the cables to null their resistance
Test current:
Test current:
> 200mA DC for R
5 (calibration included) ; Resolution for DC current :1mA
Open-circuit voltage:
4V
V
0
12V
Insulation resistance (DC voltage)
Test voltage[V]
Range [M
]
Resolution [M
]
Accuracy
50
0.01
9.99
0.01
(2.0rdg + 2dgt)
10.0
49.9
0.1
50.0
99.9
0.1
(5.0rdg + 2dgt)
100
0.01
9.99
0.01
(2.0rdg + 2dgt)
10.0
99.9
0.1
100.0
199.9
0.1
(5.0rdg + 2dgt)
250
0.01
9.99
0.01
(2.0rdg + 2dgt)
10.0
99.9
0.1
100
499
1
(5.0rdg + 2dgt)
500
0.01
9.99
0.01
(2.0rdg + 2dgt)
10.0
199.9
0.1
200
499
1
500
999
1
(5.0rdg + 2dgt)
1000
0.01
9.99
0.01
(2.0rdg + 2dgt)
10.0
199.9
0.1
200
999
1
1000
1999
1
(5.0rdg + 2dgt)
Open-circuit voltage:
nominal test voltage –0% +10%
Short circuit current:
<6.0mA at 500V test voltage
Nominal test current:
>1mA if load= 1k
*Vnom (Vnom=50V, 100V, 250V, 500V, 1000V)
Safety protection:
the display shows an error message for input voltage >10V
Z Line (Line-Line, Line-Neutral, Line-PE)
Range [
]
Resolution [
]
Accuracy
0.00
199.9
m
(*)
0.1
m
(*)
(5.0 rdg + 1
m
)
(*)
200
1999
m
(*)
1
m
(*)
0.01
9.99
0.01
(5.0 rdg + 3dgt)
10.0
199.9
0.1
(*) By means of IMP57 optional accessory
Maximum test current:
Maximum test current:
5.81A (at 265V); 10.10A (at 457V)
Test voltage ranges:
100
265V (Line-Neutral) / 100460V (Line-Line); 50/60Hz 5%
Protection type:
MCB (B, C, D, K), Fuse (gG, aM)
Insulation materials:
PVC, Rubber butyl, EPR, XLPE
First fault current (IT systems)
Range (mA)
Resolution (mA)
Accuracy
0.1
0.9
0.1
(5.0 rdg + 1dgt)
1
999
1
(5.0 rdg + 3dgt)
Limit contact voltage (ULIM) :
25V, 50V