Fluke 1653B05-TPOLEKIT/FVDE-tester 4426033 User Manual

Product codes
4426033
Page of 66
 Electrical 
Installation 
Tester 
 Making 
Measurements 
25 

 Warning 
The symbol 
 on the LCD indicates the high current loop 
mode - any RCDs in the system will trip - ensure there are no 
RCDs present. 
Earth Resistance Testing by Loop Method 
You can also use the tester to measure the earth resistance component of the 
total loop resistance. Check your local regulations to determine if this method is 
acceptable in your area. You can use three leads or the mains cord to perform 
this test. Use the connection shown in Figure 13 when making a 3-wire 
connection for earth resistance loop test. Zero the test leads (see sequence for 
Loop Impedance measurement).  
L
N
PE
PE (Green)
L (Red)
N
 (Bl
u
e)
 
apx024f.eps 
Figure 13. 3-Wire Connection for Earth Resistance Loop Test 
To measure earth resistance using the loop test no trip mode: 
1.  Turn the rotary switch to the 
 
position. 
2. Press 
 to select L-PE. 
3. Press 
 to select RE (resistance). 
4.  Press and release . Wait for the test to complete. 
 
The primary (upper) display shows the loop impedance. 
 
The secondary (lower) display shows the earth resistance. 
Line Impedance 
Line impedance is source impedance measured between Line conductors or 
Line and Neutral. This function allows the following tests: 
 
Line to Neutral loop impedance. 
 
Line to Line impedance in 3-phase systems.