 Electrical 
Installation 
Tester 
 
Maintaining the Tester 
43 
Testing the Fuse 
A fuse test is performed each time you turn on the tester. If leads are plugged 
into the L and PE terminals, the fuse test is skipped. If a blown fuse is detected, 
testing is disabled, FUSE appears on the primary display, and the tester issues 
a warning beep. 
You can also perform a manual check of the fuse. 
To manually check the fuse: 
1.  Turn the rotary switch to either  or  switch setting. 
2.  Short the leads and press and hold . 
3.  If the fuse is bad, FUSE will appear on the display to indicate the tester is 
damaged and needs repair. Contact Fluke Service for repair (see 
Contacting Fluke).