Fluke 1652C07-TPOLEKITVDE-tester 4426040 User Manual

Product codes
4426040
Page of 66
1652C/1653B/1654B 
Users Manual 
54 
Tripping Speed Test (
Δ
T) 
RCD Current Selection 
Test Function 
10 mA  30 mA 100 mA
[1]
300 mA
[1]
500 mA
[1]
1000 mA
[2]
var
[3]
 
x ½, 1 
 
 
 
 
 
 
 
x 5 
 
 
 
 
 
 
 
Ramp 
 
 
 
 
 
 
 
Auto 
 
 
 
 
 
 
 
Notes 
Mains voltage 100 V – 265 V ac, 50/60 Hz 
[1]  Type B RCDs require mains voltage range of 195 V – 265 V. 
[2]  Type AC RCDs only. 
[3]  Type A RCDs are limited to 700 mA, not available for Type B RCDs. 
 
Measurement Range 
Current 
Multiplier 
*RCD Type 
Europe UK 
Trip Time Accuracy 
x ½ 
310 ms 
2000 ms 
±
(1 % Reading + 1 ms) 
x ½ 
510 ms 
2000 ms 
±
(1 % Reading + 1 ms) 
x 1 
310 ms 
310 ms 
±
(1 % Reading + 1 ms) 
x 1 
510 ms 
510 ms 
±
(1 % Reading + 1 ms) 
x 5 
50 ms 
50 ms 
±
(1 % Reading + 1 ms) 
x 5 
160 ms 
160 ms 
±
(1 % Reading + 1 ms) 
Notes 
*G – General, no delay 
*S – Time delay 
Maximum Trip Time 
The RCD  symbol switches on when testing the RCD trip time if the trip time meets the 
following conditions: 
RCD  
Δ N
 Trip 
Time 
Limits 
AC G, A, B 
x 1 
Less than 300 ms 
AC G-S, A-S, B-S 
x 1 
Between 130 ms and 500 ms 
AC G, A, B 
x 5 
Less than 40 ms 
AC G-S, A-S, B-S 
x 5 
Between 50 ms and 150 ms