Testboy TV 455VDE-tester Testboy TV 455 User Manual

Product codes
Testboy TV 455
Page of 76
TESTBOY TV 450 
Settings 
 
26 
Maximum test times related to selected test current for general (non-delayed) RCD 
Standard          
½
×I
ΔN
 
I
ΔN
 
2
×I
ΔN
 
5
×I
ΔN
 
EN 61008 / EN 61009 
300 ms 
300 ms 
150 ms 
40 ms 
EN 60364-4-41 
1000 ms 
1000 ms 
150 ms 
40 ms 
BS 7671 
2000 ms 
300 ms 
150 ms 
40 ms 
AS/NZ (I, II, III) 
1000 ms 
1000 ms 
150 ms 
40 ms 
 
Maximum test times related to selected test current for selective (time-delayed) RCD 
Standard          
½
×I
ΔN
 
I
ΔN
 
2
×I
ΔN
 
5
×I
ΔN
 
EN 61008 / EN 61009 
500 ms 
500 ms 
200 ms 
150 ms 
EN 60364-4-41 
1000 ms 
1000 ms 
200 ms 
150 ms 
BS 7671 
2000 ms 
500 ms 
200 ms 
150 ms 
AS/NZ (IV) 
1000 ms 
1000 ms 
200 ms 
150 ms 
 
4.2.6  Isc factor 
 
 
In this menu the Isc factor for calculation of 
short circuit current in Z-LINE and Z-LOOP 
measurements can be set. 
 
Figure 4.7: Selection of Isc factor 
Keys: 
 
UP / DOWN 
Sets Isc value. 
TEST 
Confirms Isc value. 
Function selectors 
Exits back to main function menu. 
 
Short circuit current Isc in the supply system is important for selection or verification of 
protective circuit breakers (fuses, over-current breaking devices, RCDs). 
The default value of Isc factor (ksc) is 1.00. The value should be set according to local 
regulative.  
Range for adjustment of the Isc factor is 0.20 
÷ 3.00.  
 
4.2.7 Commander support  
 
The support for remote commanders can be 
switched On/ Off in this menu. 
 
Figure 4.8: Selection of commander 
support