Operating manual for the TG uni 1 appliance tester
Test procedure in accordance with VDE 0701 and 0702
9.9 Diagram 2
Test procedure for devices of protection class II and III
Visual Inspection
Protection class
II or III
Is measuring the insulation
resistance applicable?
Protection class II and touchable
conductive parts of protection class I
that are not connected to the
protective conductor
Measuring the
insulation resistance
Can the test object be
insulated from earth?
Can the test object be
insulated from earth?
Protection class II
Yes
Measuring the touch
current, differential
current method
Measuring the touch
current, direct
measurement
Measuring the touch
current, substitute
leakage current
method
Measuring the touch
current, differential
current method
Measuring the touch
current, substitute
leakage current
method
Measuring the touch
current, differential
current method
Measuring the touch
current, direct
measurement
Measuring the touch
current, differential
current method
End
Test log, test report
(documentation)
Function test and
inspection of
inscriptions
Function test, optional with VDE 0702, Fig.66
and not with PC III
Fig.45
Fig.46/47
Fig.41
Diagram M8a
Diagram M4b
Diagram M4b
Fig.41
Fig.41
Diagram M8a
Fig.41
Yes
No
Fig.5
Fig.5
No
Yes
No
Fig.35
Fig.36
Fig.35
Measuring the insulation
resistance
Diagram 3
Diagram M3