A red indicator (Fig. 2) on the left side of 
the instrument indicates the automatic 
change of range. When it is lit, multiply the 
reading by 10 to obtain the result. 
Measurement input terminals:  
These accept safety plugs 4mm in 
diameter.
 
Other indicators:  
An  orange  indicator  (Fig.  1)  on  the  right 
side  of  the  instrument  indicates  that  the 
speed of the magneto is correct. When it is 
lit, the voltage between the terminals of the 
instrument  is  500V,  650V,  or  10VDC  (no-
load),  depending  on  the  setting  of  the
switch. 
3  USE - CHARACTERISTICS: 
3.1 
RECOMMENDATIONS 
The needle must indicate 0 when at rest in the voltmeter setting; if not, adjust 
it using the black screw in the centre (see picture above). 
Do  not  connect  the  instrument  to  the  terminals  of  a  circuit  of  which  the 
voltage exceeds 600VAC or DC. 
Before any resistance measurement, check that the circuit is not live (switch 
set to voltmeter before connection). 
After  each  insulation  resistance  measurement,  let  the  circuit  discharge 
(needle  on  0V;  this  takes  a  few  seconds)  before  disconnecting  the 
instrument.