Siemens Ground fault (FI)- circuit breaker 63 A/ 0.03 A 4 pin 5SM33466KK12 Data Sheet
Product codes
5SM33466KK12
Building Technology > Low-Voltage Power Distribution and Electrical Installation
Technology > SENTRON Protection, Switching, Measuring and Monitoring Devices > Protection
Devices > Residual Current Protective Devices > 5SM3 RCCBs, Type A
Devices > Residual Current Protective Devices > 5SM3 RCCBs, Type A
5SM3346-6KK12
RCCB TYPE A 63/4 30MA 4MW IBU
Similar to image
RES.CURR. OP.CIRC. BR. SIGRES TYPE A PSE/SSF 63A
3+N-POL IFN 30MA 400V 4MW FOR SPECIAL ENVIRON.
CONDITIONS
3+N-POL IFN 30MA 400V 4MW FOR SPECIAL ENVIRON.
CONDITIONS
Technical data:
mounting position
any
Height
mm
90
Width
mm
72
Depth
mm
77
Design of the product
Instantaneous
Supply voltage / for AC / rated value
V
400
Resistance against the impulse current / rated value
kA
1
Ambient temperature
°C
-25…+45
Ambient temperature
during storage
°C
-40…+75
Mechanical operating cycles as operating time / typical
10,000
Overvoltage class
III
Supply voltage / for testing equipment / minimum
V
100
Protection against electrical shock
Finger and back-of-hand safe
Position / of power supply cord
bottom
Tightening torque
with screw-type terminals
N·m
2.5…3
Section de conducteur raccordable
solid
mm²
1.5…25
multibrin
mm²
1.5…25
Product feature
silicon-free
Yes
halogen-free
Yes
Number of test cycles / for environmental testing / in
accordance with IEC 60068-2-30
accordance with IEC 60068-2-30
28
Item designation
according to DIN EN 61346-2
F
Page 1 of 2