Lappkabel Black 15500213 Data Sheet

Product codes
15500213
Page of 1
U.I. Lapp 
GmbH 
DATA SHEET 
 
 
 
    
 
NYY-J, NYY-O
 
 
DB 1550030 
valid from:  2014-02-10 
 
 
Originator: KASC / PDC
 
approved:  HAPF / PDC 
Document: 
DB1550030EN 
Page 1 of 1 
All rights reserved acc. to DIN ISO 16016.  
PD 0019/2.2_11.10EN 
Application 
 
NYY are cables with an insulation and an outer sheathing of PVC. They are used for fixed installation in dry or damp rooms 
as well as outdoors, underground and under water. Multicore cables have a common core covering over the twisted cores or 
a filler. 
 
 
Design 
 
Design 
based on 
 
DIN VDE 0276-603 VDE 0276-603 (for 1 to 5 cores) 
 
DIN VDE 0276-627 VDE 0276-627 (as from 7 cores) 
 
 
Conductor 
round, single- or multi-wire, 
 
strands of copper acc. to IEC 60228 resp. VDE 0295, class 1 
 
Core insulation 
PVC compound DIV4 acc. to
 
DIN VDE 0276-603 VDE 0276-603 
 
Core identification 
up to 5 cores: colour coded acc. to DIN VDE 0293-308 VDE 0293-308 
 
from 6 cores: black with white numbers 
 
Outer sheath 
PVC compound DMV5 acc. to DIN VDE 0276-603 VDE 0276-603       
 
colour: black 
 
 
Electrical properties  
 
Nominal voltage 
/ U  600 / 1000 V 
 
Test voltage 
4000 V AC 
 
 
Mechanical and thermal properties 
 
Min. bending radius 
single core: 
   
15 x outer diameter 
 
 
 
multi core: 
              12 x outer diameter 
 
Temperature range 
during installation:   
  -5 °C up to +50 °C max. conductor temperature 
 
fixed installation:  
-40 °C up to +70 °C max. conductor temperature 
 
Flammability 
flame retardant acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2  
 
EC directive
 
This cable is conform to ECD 2006/95/EC (Low Voltage Directive) and 2011 / 65 / EU 
 
(RoHS, Restriction of the use of certain hazardous substances).