Faber Kabel Orange 010966 Data Sheet

Product codes
010966
Page of 2
DBL_NH9.PDF Issue 01.11.2013 Klaus Faber AG, 66113 Saarbrücken, Lebacher Str. 152-156, Tel.: (0681) 9711-0, FAX: - 289
FRNC power cable NHXH
 FE180/E90 acc. to VDE 0266
conductor material:
bare copper 
conductor construction:
class 1, from 25 sqmm class 2  
insulation:
FRNC compound HI1 
sheathing material:
FRNC-compound HM1 
flame retardant:
VDE 0482-266-2-4/IEC 60332-3-24 
smoke density:
DIN EN 61034/IEC 61034 
halogen free:
DIN EN 50267/IEC 60754 
fire resistance:
FE 180 (IEC 60331) 
circuit integrity:
E 90 
maximum temperature at
conductor:
90 °C
max. operating temperature,
fixed:
-5 - +70 °C
bending radius, fixed
installation:
12 x DA
nominal voltage Uo:
600 V
nominal voltage U:
1 kV
maximum permitted
operating voltage in 3-phase
systems:
1,2 kV
test voltage:
4 kV
core identification:
colours acc. VDE 0293 (HD308) 
Application: For installation in dry and wet rooms, also for direct bedding in concrete, butnot for direct burial in ground
and not for use in water. The cable has improved flame retardant and may be used in public buildings with high safety
requirements. Cables are halogen free, low smoke density and are fire resistant according to VDE 0472 part 814
(180 min., = IEC 331) Furthermore the cable passed the test of 90 min. circuit integrity according to DIN 4102 part
12 (E 90) for all so called standard-installation systems (ladder, tray and ceiling) and is suitable for installation in fire
alarm systems, safety lightning and other emergency electrical supply systems according to VDE 0108. A special test
certificate about the circuit integrity is issued by the "Amtlichen Materialprüfanstalt für das Bauwesen". For calculation
of electrical systems with circuit integrity has to bee considered that electrical resistance of copper conductors at 1000
°C is approximately 4,5 times higher than at 20 °C and the current carrying capacity has to be reduced respectively.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics NHXH-J/-O E90
p/n
part name
.
R
l
.
[Ω/km]
I
bl
.
[A]
R
bv
.
[mm]
D
A
.
[mm]
Cu
.
[kg/km]
G
.
[kg]
012020
NHXH-O E90 01X16 OR
1,15
131
165
10,5
154
230
012021
NHXH-O E90 01X25 OR
RM
0,727
177
195
12,5
240
340
012022
NHXH-O E90 01X35 OR
RM
0,524
217
210
13,5
336
440
011757
NHXH-O E90 01X50 OR
RM
0,387
265
240
13,9
480
600
011843
NHXH-O E90 01X70 OR
RM
0,268
336
270
16,5
672
800
011756
NHXH-O E90 01X95 OR
RM
0,193
415
300
18,9
912
1100