APPLICATION
Time control for isolated applications.
DESCRIPTION
The  BMRF  multifunction  timer  offers  8  selectable  timing 
functions and 8 different timing intervals in one unit. 
Depending on the chosen settings timing commences with the 
connection  of  the  power  supply  or  contact  controlled  on 
terminals B1/B2 or voltage controlled on terminals B1/B2.
B1/B2/P1/P2  is  galvanic  isolated  from  the  supply 
terminals A1/A2/A3 by a switch mode power supply.
OPTION
Other timing ranges or supply voltages upon request.
MOUNTING
Useable at any mounting position.
APPROVALS
The  function  and  timing  intervals  can  be  adjusted  with  DIP 
switches on the front panel of the relay.   The multi-function 
timer  can  operate  on  either  AC  or  DC  voltage  using  two 
separate connections.   For a 230V AC power supply use the 
terminals  A1/A2.    For  a  24V  UC  power  supply  use  the 
terminals A3/A2.   The green LED indicates the connection of 
the power supply.
Snap-on mounting using a standard DIN rail EN 50022. 
The unit is designed to allow side-by-side mounting, with an 
ambient temperature of < 60°C. 
 
H S B
Industrieelektronik
FUNCTION
Delay-on operate : Timing begins with the connection of the 
power supply. This is indicated by a flashing yellow LED. After 
set time has elapsed the output relay switches into ist working 
position. This is indicated by a permanent on yellow LED. This 
state  will  be  set  untill 
the  supply  voltage  is  disconnected. 
Should  the  power  supply  be  disconnected  during  recovery 
time, the timer returns to its original state.  This also applies if 
the supply is disconnected during the timing period.
PART NUMBER
011125
BMRF   
contact controlled
011127
BMRFV
voltage controlled
              
t
t
t
time
A1 (A3) / A2
Kontakt   15,18
Kontakt   15,16
15
A1
A2
16 18
A3
Multifunction timer BMRF, BMRFV
Serie 22,5mm
2 changeover with galv. isolation and remote potentiometer terminal 
DIP SWITCH ADJUSTMENT
* for ext. potential free control contact
TIME ADJUSTMENT
Setting of time ranges has to be done by DIP switch on the 
front  panel.  Fine  adjustment  has  to  be  done  by  internal 
potentiometer or by an external potentiometer.
The  connection  of  an  external  potentiometer  to  the 
terminals P1/P2 does lock the internal potentiometer.
This means that the value of the internal potentiometer 
has no effect to the time settings.
Terminals  B1/B2  just  as  terminals  P1/P2  are  galvanic 
isolated from the supply voltage terminals A1/A2/A3.
So you can use a usual 10kOhm potentiometer for remote 
fine adjustment.
flasher
beginning with pulse
6
5
4
3
2
1
 T
ime
 Function 
3
3
3
3
3
2
2
2
2
2
delay-on operate
delay-on release
*
pulse-on operate
pulse-on release
*
1
1
1
1
1
6
5
6
5
6
5
6
5
6
5
6
5
4
4
4
4
4
4
0,01  -   1 s
0,1  -  10 s
0,01  -  1 m
0,1  -  10 m
0,01  -  1 h
3
2
1
3
2
1
3
2
1
flasher
beginning with pause
3
2
1
0,1  -  10 h
watchdog
1  -  100s
1  -  100m