1. S1DXM-A multi-range timer
Power ON-delay operation
• When power is turned on, the output contact operates after the set time. The output contact remains on until the power is turned off.
2. S1DXM-M multi-range timer
TIME RANGE SETTING
Note: The time setting range is the combination of the time scale (X1 or X10) on the dial and the time unit (s, m, or h). 
Example: When dial reads 1, time scale is X1 and time units is seconds, then it is 1 second.
ORDERING INFORMATION
Type
Time scale
Time unit
Min. scale
Max. scale
Setting range
S1DXM-A
10M type
X1
X10
s
m
0.05
1
0.05 to 1s
0.5 to 10s
0.05 to 1m
0.5 to 10m
30M type
s
m
0.2
3
0.2 to 3s
2 to 30s
0.2 to 3m
2 to 30m
60M type
s
m
0.5
6
0.5 to 6s
5 to 60s
0.5 to 6m
5 to 60m
10H type
m
h
0.05
1
0.05 to 1m
0.5 to 10m
0.05 to 1h
0.5 to 10h
S1DXM-M
10M type
X1
X10
s
m
0.05
1
0.05 to 1s
0.5 to 10s
0.05 to 1m
0.5 to 10m
30M type
s
m
0.2
3
0.2 to 3s
2 to 30s
0.2 to 3m
2 to 30m
60M type
s
m
0.5
6
0.5 to 6s
5 to 60s
0.5 to 6m
5 to 60m
10H type
m
h
0.05
1
0.05 to 1m
0.5 to 10m
0.05 to 1h
0.5 to 10h
T
T: Setting time
Power supply
Time chart
Timed-out contact (NO)
UP (operation) LED
ON (power) LED
(orange)
OFF
(green)
ON
OFF
ON
Power ON-delay operation
[MODE] switch 1: OFF, switch 2: OFF
• When power is turned on, the output contact operates after the set time. 
The output contact remains on until the power is turned off.
Power Flicker OFF start operation
[MODE] switch 1: OFF, switch 2: ON
• When the power is turned on, the output contacts repeatedly operate at 
the set time. The output contact begins from the off state.
T
T: Setting time
Power supply
Time chart
Timed-out contact (NO)
UP (operation) LED
ON (power) LED
(orange)
OFF
(green)
ON
OFF
ON
T
T
T
T
T
T
t
t < T
T: Setting time
Power supply
Time chart
Timed-out contact (NO)
ON (power) LED
UP (operation) LED
(orange)
OFF
(green)
ON
OFF
ON
Power Flicker ON start operation
[MODE] switch 1: ON, switch 2: OFF
• When power is turned on, the output contact operates repeatedly at the 
set time. The output contact outputs at the same time power turns on.
Power One-shot operation
[MODE] switch 1: ON, switch 2: ON
When power is turned on, the output contact performs the on operation 
at the same time power turns on, only for the set time.
T
T
T
T
T
T
t
t < T
T: Setting time
Power supply
Time chart
Timed-out contact (NO)
ON (power) LED
UP (operation) LED
(orange)
OFF
(green)
ON
OFF
ON
T
T: Setting time
Power supply
Time chart
Timed-out contact (NO)
ON (power) LED
UP (operation) LED
(orange)
OFF
(green)
ON
OFF
ON
Operation mode
A
M
Control output
arrangement
2C: Timed-out 2 Form C
4C: Timed-out 4 Form C
Time range
10M: 
30M: 
60M: 
10H: 
0.05 s to 10 min
0.2 s to 30 min
0.5 s to 60 min
0.05 min to 10 hr
DC12V: 
DC24V: 
AC24V: 
AC120V: 
AC220V: 
AC240V: 
12 V DC
24 V DC
24 V AC
100 to 120 V AC
200 to 220 V AC
220 to 240 V AC
Operating voltage*
* For other operating voltage types, please consult us.
A
2C
30M
DC24V