Tele 110200 Time Delay Relay, Timer, 1 CO contact 12 - 240 V DC/AC 110200 Data Sheet

Product codes
110200
Page of 2
Subject to alternations and errors
Release 10/05
Timers - ENYA series
Timers multifunctional
Up to 7 functions
7 time ranges
Wide input voltage range
1 change over contact
Width 17.5 mm
Installation design
Technical data
1. Functions
The function has to be set before connecting the relay to the supply 
voltage. 
 E 
ON 
delay
 R 
OFF 
delay
 
Ws 
Single shot leading edge with control input
 
Wa 
Single shot trailing edge with control input
 
Es 
ON delay with control input
 
Wu 
Single shot leading edge voltage controlled
 
Bp 
Flasher pause first
 
Function sets of the distinct types are according to table
 
ordering information or printing on the unit.
2. Time ranges
Time range 
Adjustment range
 1s 
50ms 
1s
 10s 
500ms  10s
 1min 
3s 
1min
 10min 
30s 
10min
 1h 
3min 
1h
 10h 
30min  10h
 100h 
5h 
100h
3. Indicators
Green LED U/t ON: 
indication of supply voltage
Green LED U/t flashes:  indication of time period
Yellow LED R ON/OFF:  indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4 (PZ1 required),  
IP rating IP20
Tightening torque: 
max. 1Nm
Terminal capacity:
 
1 x 0.5 to 2.5mm² with/without multicore cable end
 
1 x 4mm² without multicore cable end
 
2 x 0.5 to 1.5mm² with/without multicore cable end
 
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage: 
       terminals A1(+)-A2
Types E1Z..12-240VAC/DC:   12 to 240V AC/DC
 
Tolerance: 
       12V-10% to 240V+10%
Types E1Z..24-240VAC/DC:   24 to 240V AC/DC
 
Tolerance: 
       24V-15% to 240V+10%
Rated consumption: 
       4VA (1.5W)
Rated frequency: 
       AC 48 to 63Hz
Duty cycle: 
       100%
Reset time: 
       100ms
Residual ripple for DC:         10%
Drop-out voltage: 
       >30% of minimum rated supply voltage
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
6. Output circuit
1 potential free change over contact
Rated voltage: 
250V AC
Switching capacity: 
2000VA (8A / 250V)
Fusing: 
8A fast acting
Mechanical life: 
20 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency: 
max. 60/min at 100VA resistive load
 
max. 6/min at 1000VA resistive load
 
(according to IEC 947-5-1)
Overvoltage category: 
III. (according to IEC 60664-1)
Rated surge voltage: 
4kV
7. Control input
Input not potential free: 
terminals A1-B1
Loadable: yes
Max. line length: 
10m
Trigger level (sensitivity): 
automatic adaption to supply voltage
Min. control pulse length: 
DC 50ms / AC 100ms
8. Accuracy
Base accuracy: 
±1% of maximum scale value
Adjusting accuracy: 
<5% of maximum scale value
Repetition accuracy: 
<0.5% or ±5ms
Voltage influence: 
-
Temperature influence: 
≤0.01% / °C
9. Ambient conditions
Ambient temperature: 
-25 to +55°C (according to IEC 68-1)
Storage temperature: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(according to IEC 721-3-3 Klasse 3K3)
Pollution degree: 
2, if built-in 3
 
(according to IEC 664-1)
Vibrations resistance: 
10 to 55 Hz 0.35mm
 
(according to IEC 68-2-6)
Shock resistance: 
15g 11ms
 
(according to IEC 68-2-27)
10. Dimensions
11. Weight
Single packing: 
 
72g
Package 10pcs: 
 
670g per Package
E1ZM, E1Z1
17,5mm
60mm
87m
m
44mm
5mm
45mm