Phoenix Contact Current transducers MCR-SL-S-100-U 2813457 2813457 Data Sheet

Product codes
2813457
Page of 5
Nov 13, 2013    1 / 5
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
MCR current measuring transducer, for measuring sinusoidal and non-sinusoidal alternating currents,
input current 0...100 A, output voltage 0...(5) 10 V
 
Product Features
 Can be retrofitted with open-up Rogowski coil
 Loop-powered
 30 
6000 Hz true r.m.s. value measurement
 Measuring range selection via slide switch
  
Key commercial data
package_quantity
1
GTIN
4046356043632
Technical data
Dimensions
Width
55 mm
Height
85 mm
Depth
70.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
Degree of protection
IP20
Input data
Input
Current measuring input
Input current range
0 A ... 100 A (0...50/75/100 A)
Operate threshold
1 % (of final value)
Setting range for min. input current
0 A ... 50 A
Setting range for max. input current
0 A ... 100 A
Overload capacity
Depending on laid conductor
Surge strength
Depending on through connected conductor
Frequency measuring range
30 Hz ... 6000 Hz
Connection method
Clamp-on cable design, diameter 18.5 mm