Phoenix Contact Isolation amplifier MACX MCR-EX-SL-2NAM-R-UP-SP 2924249 2924249 Data Sheet

Product codes
2924249
Page of 7
Nov 14, 2013    1 / 7
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
The illustration shows the
versions with screw connection
2-channel Ex-i NAMUR isolation amplifier with wide-range power supply for proximity sensors and
switches. Every channel has a relay with PDT contact as a signal output. Line fault detection (LFD),
3-way isolation, SIL 2.
 
Product Features
 Up to SIL 2 according to EN 61508
 Installation in zone 2, protection type "n" (EN 60079-15) permitted
 Line fault detection (LFD), can be activated/deactivated, error indicated by red flashing LED with de-excitation of output relay
 Wide-range power supply of 19.2 ... 253 V AC/DC
 Direction of operation can be selected (operating or closed circuit current behavior)
 LED indicators for supply voltage, switching state, and malfunction according to NAMUR NE 44
 Relay signal output (PDT)
 Input for NAMUR proximity sensors (EN 60947-5-6), floating contacts or contacts with resistance circuit, [Ex ia] IIC
 3-way electrical isolation
 2-channel
   
  
Key commercial data
package_quantity
1
GTIN
4046356463683
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the
download area
Dimensions
Width
17.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C