Phoenix Contact Isolating amplifier MINI MCR-SL-U-I-4-SP 2813583 2813583 Data Sheet

Product codes
2813583
Page of 6
Nov 13, 2013    2 / 6
Technical data
Input data
Voltage input signal
0 V ... 10 V
Max. input voltage
30 V
Input resistance of voltage input
approx. 100 kΩ
Output data
Configurable/programmable
No
Current output signal
4 mA ... 20 mA
Max. output current
28 mA
Load/output load current output
≤ 500 Ω
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-
ST-3,81 GN, Order No. 2869728) can be used to bridge the supply
voltage. It can be snapped onto a 35 mm DIN rail according to
EN 60715))
Max. current consumption
< 20 mA
Power consumption
< 480 mW
Connection data
Connection method
Spring-cage conn.
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Stripping length
8 mm
General
Maximum transmission error
≤ 0.1 % (of final value)
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
approx. 100 Hz
Step response (10-90%)
approx. 3.5 ms
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Pollution degree
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
green