MCR loop-powered isolator for the electrical isolation of current signals without auxiliary power, input
signal: 0(4) ... 20 mA, output signal: 0(4) ... 20 mA
 
Product Features
 0/4 
20 mA current signals
 Electrical isolation without additional auxiliary voltage
 Safe isolation
  
Key commercial data
package_quantity
1
GTIN
4017918190804
Technical data
Dimensions
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-10 °C ... 70 °C
Degree of protection
IP20
Input data
Description of the input
Current input
Configurable/programmable
No
Current input signal
0 mA ... 20 mA
Current input signal
4 mA ... 20 mA
Max. input voltage
30 V (30 V overload)
Max. input current
50 mA (100 mA overload)
Response current
< 50 µA
Input voltage limitation
33 V 5 % (with Zener diode)
Voltage dissipation
2.5 V (at I = 20 mA)