Lappkabel Data cable UNITRONIC® LiYCY (TP) 12 x 2 x 0.14 mm² Grey 0035135 Sold per metre 0035135 Data Sheet

Product codes
0035135
Page of 1
DATA SHEET 
0035131 
 
UNITRONIC
®
 LiYCY   (TP) 
valid from : 
04.09.2006 
 
elaborated by:
 
TE-K:      N. Ensslen  
Document: 
DB0035131_2EN 
page 1 of 1 
 
Nr.: 0019/0894 
 
 
Application  
 
UNITRONIC
 
LiYCY  (TP) is a screened, paired, flexible cable for control and data transmissions, for weak-
current applications. The fine wired conductor (7-wired for 0.34mm
2
) and the robust ductile outer sheath gives the 
cable strength as well as high flexibility. By the pair twisting the electric circuits are well decoupled and with the 
screen of a tinned copper braiding the cabel is protected against external electrical influences. 
 
The cable is intended for static laying and flexible use in dry and damp interiors. Design and electrical 
characteristics similar to VDE 0812. 
 
 
Design 
 
Conductor 
fine-wire strands of bare copper wire; 0.14 mm² to 1.5 mm² , 7-wired for 0.34 mm²  
Insulation 
PVC compound YI2 according to VDE 0207 part 4,  
Coding 
according to DIN 47100 
Pair stranding  
cores twisted into pairs 
Core stranding 
pairs twisted in layers, wrapping by plastic foil 
Screening 
braiding of tinned copper wires, coverage approx. 85% 
Sheath 
PVC YM2 according to VDE 0207 part 5, flame retardant, grey, RAL 7032  
 
Marking on the sheath  
 
 
 
LAPP KABEL  
 UNITRONIC
®
 LiYCY   (TP)  
ART. 0035131 
 
 
Technical Data 
 
Conductor 
Loop resistance 
Mutual capacitance *) 
Impedance **)at 
cross section 
 
core/core  800 Hz 
50 kHz 
100 kHz 
≥ 1 MHz 
[mm²] 
[max.Ω/km] 
[nom. pF/m] 
nom.[Ω] 
nom.[Ω] 
nom.[Ω] 
 
 
 
 
 
 
0,14 
148 
95 
115 
93 
76 
0,25 
79,9 
97 
110 
90 
74 
0,34 
57,5 
97 
108 
90 
74 
0,5 
38,9 
100 
98 
85 
70 
0,75 
26 
112 
89 
75 
65 
1,0 
19,5 
125 
83 
70 
62 
1,5 
13,3 
135 
74 
62 
55 
 
 
Inductivity 
 
mH/km 
appr.  0.65 
Specific insulation resistance 
 
min. GΩxcm 
20 
Operating Voltage for 0.14 mm²  (not for power purposes) 
350 
 
 
   for ≥ 0,25 mm² (not for power purposes) 
500 
Test voltage  
   for 0.14 mm² 
 
U
eff.
  V 
1200 
 
 
for ≥ 0,25 mm² 
 
U
eff.
  V 
1500 
Temperature range 
static 
°C 
- 40 to + 80 
 
moved 
 
- 5 to + 70 
Minimum bending radius 
static 
 
  6 x Ø cable  
 
moved 
 
15 x Ø cable  
Flame propagation 
 
flame retardant to VDE 0482, part 265-2-1 / IEC 60 332-1 
 
*) valid for 4 pairs and more 
**) values for  f ≥ 1 MHz are for the orientation, because the cables are only limited suitable for f ≥  500 kHz