Crydom DR24D06R SeriesOne DIN Rail Mount Solid State Relay DR24D06R Data Sheet

Product codes
DR24D06R
Page of 6
Other Crydom products and competitive part number cross-reference available at:
www.crydom.com
SeriesOne DR Dual Channel
AC Output
Two independent 6 Amp channels
DIN rail mount 18 mm wide package
4-32 VDC control input
24 to 600 VAC operating voltage ratings
IP20 housing with unique integrated heat sink design (Patent Pending)
AC Output versions with Zero Voltage Turn-On for resistive loads and Random Turn-On for inductive loads
High power density for multiple units
UL & cUL approved including General Purpose and Motor Controller ratings
CE & RoHS compliant
OUTPUT SPECIFICATIONS
DRD24D06
DRD48D06
Operating Voltage (47-63Hz) [VAC]
24-280
48-600
General Use Current Rating      (Resistive Load)
6 Arms per channel
6 Arms per channel
Minimum Load Current [Arms]
0.15
0.15
MaximumOff-State Leakage Current @ Rated Voltage [mArms]
0.1
0.2
Maximum Surge Current [Apk] @ 50 Hz (Duration in ms)
715 (20)
715 (20)
Maximum Surge Current [Apk] @ 60 Hz (Duration in ms)
750 (16.6)
750 (16.6)
Transient Overvoltage [Vpk]
600
1200
Maximum On-State Voltage Drop @ Rated Current [Vpk]
1.3 
1.3
Maximum I²t for Fusing (10/8.3 ms) [A²sec]
2560/2330
2560/2330
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/μsec] 
500
500
Maximum Turn-On Time
1/2 cycle
1/2 cycle
Maximum Turn-Off Time  
1/2 cycle
1/2 cycle
UL Motor Controller Ratings @ 240 VAC [HP]
1/6
1/6
Power Factor (Minimum) with Maximum Load
0.5
0.5
DRDxxD06
DRDxxD06
Control Voltage Range [VDC]
4-32
Min. Turn-On Voltage [VDC] 
4
Min. Turn-Off Voltage [VDC] 
1
Yes
Typical Input Current
10 mA @ 24 VDC
INPUT SPECIFICATIONS
Reverse Polarity Protection
Weight (typical) [oz] (gr)
Housing Material
Input Terminal Wire Capacity 
10
-30 to 80
-30 to 125
4.4 (0.5) / 7.0 (0.8)
3.17 (90)
UL 94 V0 Self-extinguishing
22 AWG minimum, 16 AWG maximum
Output Terminal Wire Capacity 
22 AWG minimum, 14 AWG x 2 or 12AWG x1 (standed/solid) maximum
 2500
 2500
10
9
GENERAL SPECIFICATIONS
Dielectric Strength, Input to Output (50/60Hz) [Vrms]
Dielectric Strength, Input-Output to Case (50/60Hz) [Vrms]
Minimum Insulation Resistance (@ 500 VDC) [Ohm]
Maximum Capacitance, Input/Output [pF]
Ambient Operating Temperature Range [°C]
Ambient Storage Temperature Range [°C]
Maximum Recommended Terminal Screw Torque Input/Output [in/lbs] (Nm)
All parameters at 25°C unless otherwise specified.
Minimum spacing required between devices (see derating curves).
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1.
Turn-On time is 0.1 ms for Random-type DC Control Models.
Input circuit incorporates active current limitation.
GENERAL NOTES
(A)
(B)
(C)
(D)
(F)
(A)
(B)
(C)
(D)
(F)
(A)
(A)
06
24
D
DRD
Series
Max Output Voltage
24:
48:
Control Voltage
D:
Output Current
06:
24 to 280 VAC
48 to 600 VAC
4 to 32 VDC
6 Amps
Options
Blank: Zero Voltage Turn-On
R: Random Turn-On
Required for valid part number
For options only and not required
for valid part number
R
Part Number Nomenclature
ID Marker Strips
CNLB, CNLN, CNL2
Blank Strips
Part no.: CNLB
Packages of 10 plastic strips comprising
10 individual markers which can be
placed for easy identification during
the use of multiple units.
Numbered 1 to 10 Strips
Part no.: CNLN
Numbered 11 to 20 Strips
Part no.: CNL2