SALUS RT 10
Electronic room thermostat for radiant panel, 
radiator and convector heating systems
Installation and 
operating instructions
General
Congratulations  on  choosing  to  purchase 
a  SALUS  room  thermostat.  In  selecting  the 
room  temperature  controller  that  can  boast 
some considerable advantages over its con-
ventional,  mechanical  counterparts.  This 
controller is very simple to use with its stan-
dard rotary knob and, with its state-of-theart 
electronics, it can offer you unparalleled ease 
of control for all manner of heating systems. 
The  RT 10‘s  features,  which  are  described 
in detail below, ensure that you can control 
your  heating  system  in  a  precise,  easy  and 
energy-saving way.
Technical characteristics
Pulse width modulation (PWM) 
Radiant panel heating systems tend to have a 
problem with overshooting, i.e. rooms conti-
nue to be heated even after the desired tem-
perature has been reached and the valve has 
been closed. The RT 10 solves this problem 
electronically and especially effectively using 
what is known as pulse width modulation. By 
continuously comparing set temperature with 
actual  temperature,  the  lengths  of  opening 
times  for  the  valve  actuators  are  regulated 
in such a way that the temperature is almost 
completely prevented from exceeding or fal-
ling below the set temperature. In this way, 
the required temperature setting is regulated 
in a precise and convenient way. 
Note:  When  the  RT 10  is  used  with  radiator 
or  convector  heating  systems,  pulse  width 
modulation can be switched off if necessary 
(see ‚Basic settings‘ section). 
Valve protection function
To  ensure  that  valves  remain  movable  and 
ready for use even when they are unused for 
considerable periods – e.g. over the summer 
– the RT 10 includes a valve protection func-
tion. Briefly once a week, even when there is 
no requirement for any heat, the valve actua-
tors open the valves that they control.
Note:  The  valve  protection  function  can  be 
switched  off  if  it  is  not  required  (see  ‚Basic 
settings‘ section).
Temperature reduction
Timed and demand-oriented heating control 
are amongst the best ways of managing hea-
ting energy in an economical way. The RT10 
has  an  integrated  temperature  reduction 
function which enables you to automatically 
reduce  the  set  temperature  by  4K  with  no 
need for any costly add-on installation on the 
boiler  controller.  This  ‚night  reduction‘  can 
be activated by an external signal, e.g. time 
control from a terminal strip, or using a stan-
dard external timer.
Installation
The  RT 10  room  thermostat  is  designed  as 
an  electronic  temperature  controller  for  the 
electrical fine adjustment of hot-water based 
heating systems, and is used for controlling 
electro-thermal valve actuators or other elec-
trical devices. It is vitally important that the 
maximum switching current specified in the 
technical specifications should not be excee-
ded! We are not liable for any form of impro-
per use.
This  equipment  must  only  be  installed  by 
anauthorised, qualified engineer, and only in 
accordance  with  the  wiring  diagram.  Instal-
lation  must  also  be  in  accordance  with  the 
latest VDE regulations as well as your electri-
city supplier‘s regulations. The system must 
be in a de-energised state whilst installation 
is  carried  out,  and  all  safety  instructions 
must be followed to the letter.
The control may only be mounted on a non-
conductive  surface.  Find  a  position  for  the 
thermostat where it is not covered by curta-
ins, furniture or anything else. The controller 
must  not  be  installed  too  close  to  any  heat 
source  (lights,  stove,  direct  sunlight  etc.), 
nor should it be installed in a position where 
it will be exposed to draughts. The control-
ler must be installed in a suitable location in 
order for room temperature to be monitored 
accurately  and  accordingly  regulated  with 
precision.
Important:  The  thermostat  must  be  dis-
connected  from  its  power  supply  before  its 
housing is opened.
Wall mounting
The  housing  cover  must  be  separated  from 
the base plate before the controller is fitted. 
Follow the steps listed below:
Carefully pull off the adjuster wheel.
1. 
Remove the screw from under the adju-
2. 
ster wheel.
Open the housing by pulling off its cover 
3. 
on the adjuster wheel (right) side.
Now,  using  the  screws  supplied,  screw  the 
base  plate  firmly  to  the  wall  or  the  flush-
mounted socket.
Connection
The thermostat must be wired in accordance 
with the wiring diagram below:
RT 10 
230 V Model
Terminal
Lead for temperature reduction 
N
Neutral conductor supply lead
L
230VAC power supply
Switch output (valve actuator, terminal 
strip)
RT 10 
24 V Model
Terminal
Lead for temperature reduction
L2
Neutral
NC
Circuit closed once temperature reached
1
Common
NO
Circuit open once temperature reached
2
L1
24VAC power supply
e.g. cooling unit  
e.g. heating unit
Basic settings
The jumpers on the PCB can be used to turn 
on or off various functions of the RT 10:
RT 10 Jumpers
Switch
Function
ON
OFF
VP
Valve protection 
function
PWM
Pulse width 
modulation
Temperature 
reduction
The factory setting for all these functions is 
ON. You can change these settings according 
to  your  own  requirements  by  moving  the 
contact terminals on the jumpers. 
Important: The contact terminals should not 
be removed. 
As long as the installation is carried out to a 
professional standard, the criteria for protec-
tion class II will be satisfied.
Operation
The  RT 10  electronic  room  thermostat  is 
used  for  regulating  the  temperature  in  dry, 
enclosed  rooms  with  a  normal  environment 
and maximum humidity of 95% (nonconden-
sing).
It is extremely simple and convenient to set 
the  desired  room  temperature  using  the 
rotary  knob.  This  electronic  control  system 
ensures  that  the  set  room  temperature  is 
maintained virtually without fluctuation and, 
when required, automatically activates a red-
uction in temperature.
Never  use  anything  other  than  a  soft,  dry 
cloth  to  clean  the  unit.  Never  use  any  clea-
ning agents containing solvents or any sharp 
objects to clean the unit!
Technical data
230 V
24 V
Product no.:
412.100
412.101
Operating voltage:
230VAC / 50Hz
24VAC / 50 Hz
Electronic switch output
Max. switching current:
10 (2) A
Rated impulse voltage:
4000 V
Max. no. of valve actuators:
5 units - 3 W
Temperature range:
5°C - 30°C
Degree of protection through casing:
IP 30
Automatic function:
type 1.C (EN 60730-1)
Degree of contamination:
2 (Household)
Dimensions W/H/D in mm:
75 / 75 / 27
Operating temperature:
0°C - 50°C
Storage temperature:
-25°C - 65°C
Control pollution:
Normal