Phoenix Contact Surge protection device UBK 2-500 2798530 2798530 Data Sheet

Product codes
2798530
Page of 5
Nov 13, 2013    1 / 5
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
The illustration shows version
UBK 2-110
DIN rail module with coarse surge protection for two signal wires. Self-contacting grounding foot for
mounting on NS 32 or NS 35/7.5, housing width: 17.5 mm. Design: 500 V AC
 
Key commercial data
package_quantity
10
GTIN
4017918073800
Technical data
Dimensions
Height
90 mm
Width
17.5 mm
Depth
46 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 80 °C
Degree of protection
IP20
General
Housing material
PA 6.6
Inflammability class according to UL 94
V2
Color
black
Standards for air and creepage distances
IEC 60664-1
Design
Rail-mountable module, one-piece
Direction of action
Line-Earth Ground
Protective circuit
IEC test classification
C2 + D1
VDE requirement class
C2 + D1
Nominal voltage U
N
500 V AC
Maximum continuous voltage U
C
 (wire-ground)
500 V AC
Nominal current I
N
2 A
Operating effective current I
C
 at U
C
≤ 1 µA
Residual current I
PE
≤ 1 µA
Nominal discharge current I
n
 (8/20) µs (Core-Earth)
10 kA