Eaton 5115 UPS
1. LED user interface
2. Panel for replacing batteries
3. 1 USB port + 1 serial port
4. Dataline (network) protection
5. 4 to 6 IEC 10A sockets
1
2
In the interests of continuous product improvement all specifications are subject to change without notice.
Technical specificaTion
Rating
500 VA
750 VA
1000 VA
1400 VA
Part number
05146549-5591
05146555-5591
05146561-5591
05146567-5591
Capacity (VA/watts)
500/320
750/500
1000/670
1400/950
Dimensions WxDxH (mm)
150x268x185
150x333x185
150x333x185
150x388x185
Weight (kg)
8
12
13
17
Input connection
IEC320/10A
IEC320/10A
IEC320/10A
IEC320/10A
Output connection
4xIEC320/10A
4xIEC320/10A
6xIEC320/10A
6xIEC320/10A
Typical runtime  (full load) 
             (half load)
5 min 
15 min
6 min 
17 min
5 min 
15 min
5 min 
15 min
Operational
Nominal input voltage (Vac)
220/230/240 Vac
Input voltage range
184-276 VAC(± 20% of nominal)
Operating frequency
50/60 Hz auto sensing 
Input power factor
Same as load
Nominal output voltage
220/230/240 Vac
Output voltage regulation
-10%/+6% of selected nominal voltage
Overload capacity
110% 3 min; 150% 10 cycles
Efficiency
95%
User interface
LED
Four LEDs; UPS on, UPS on battery, overload, alarm
Standard communication ports
RS232 & USB
Optional
External SNMP adapter
Environmental
Operating temperature
0°C - +40°C
Storage temperature
-15°C -+55°C
Altitude
<3000 m
Audible noise at 1 metre
<40 dB 
Certification
Markings
CE
Safety
IEC 62040-1, UL 1778 
EMC
IEC 62040-2
eaTon 5115 RUnTiMes foR TYpical applicaTions
Load VA / W
500 VA
750 VA
1000 VA
1400 VA
200 VA / 128 W
17
38
41
58
300 VA / 192 W
11
27
28
41
500 VA / 320 W
5
14
15
28
600 VA / 400 W
9
10
19
750 VA / 500 W
6
8
14
900 VA / 600 W
6
10
1000 VA / 670 W
5
8
1200 VA / 800 W
6
1400 VA / 950 W
5
1
2
© 2011 Eaton Corporation, All Rights Reserved, Printed in Finland, 00DATA1018104 rev B, December 2011
5
4
3
www.eaton.com/powerquality