Lappkabel 0183006, Single Core Wiring Cable, , AWG, Green Sheath 0183006 Data Sheet

Product codes
0183006
Page of 1
DATA SHEET 
0181000 
 
ÖLFLEX
®
 
HEAT 145 SC / single core 
valid from : 
04.12.2007
 
 
elaborated by:
 
TE-K:     M. Herb / R. Krämer 
Document: 
DB0181000EN 
page 1 of 1 
 
Nr.: 0019/0894 
 
Application 
 
ÖLFLEX
®
 HEAT 145 SC are heat resistant single core cables, insulated with a cross-linked, halogen-free poly-
olefin copolymer compound with excellent mechanical characteristics. Further special features: Large tempera-
ture range, good UV-light- and oil resistance, halogen-free, low smoke density and low toxicity of the smoke 
gases in case of fire.  
Typically used for and in railways, locomotives, trams, busses or any other kind of public transport systems, in 
subways/underground, for inside wiring of lamps, heating appliances, electrical machines and in any kind of plant 
and machinery construction. 
 
 
Design 
 
Conductor 
fine wire strand of tinned copper acc. to IEC 60228 resp. VDE 0295, class 5 
 
Core insulation 
cross-linked polyolefin copolymer, halogen free 
 
Core identification 
individual colours 
 
 
Electrical properties at 20 °C 
 
Nominal voltage 
up to 1, 0 mm²: 300 / 500 V 
 
from 1, 5 mm²:  450 / 750V,  
 
 
for fixed and protected installation from 1, 5 mm² :  0,6 / 1 kV  
 
Test voltage 
 
3500 V AC 
 
 
Mechanical and thermal properties 
 
Temperature range 
fixed installation        -55 °C to +125 °C max. conductor temperature 
 
 
for flex. applications  -35 °C to +120 °C max. conductor temperature 
 
 
for short time up to                   +145 °C max. conductor temperature 
 
Min. bending radius 
4 x cable diameter for fixed installation 
 
Flammability 
flame retardant in acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2  
 
and IEC 60332-3-24 (Cat. C) resp. VDE 0482-266-2-4   
 
Smoke density 
 
acc. to IEC 61034-2 
 
Halogen-free 
  acc. to IEC 60754-1 resp. VDE 0472 part 815 
 
Corrosivity 
  acc. to IEC 60754-2 resp. VDE 0482 part 267-2-3 
 
Chemical resistance 
oil resistance acc. to IEC 60811-2-1 resp. VDE 0473 part 811-2-1 
 
 
 
Tests  
acc. to IEC 60811-x-x resp. VDE 0473 part 811-x-x, VDE 0472 
 
EC directive 
this cable confirms to ECD 2006/95/EC  
 
(low voltage directive).