Lappkabel 4160309, Copper tin- plated Single Core Wiring Cable, , AWG, Orange Sheath 4160309 Data Sheet

Product codes
4160309
Page of 1
U.I. Lapp 
GmbH 
DATA SHEET 
 
 
 
    
 
Multi-Standard SC 2.1
 
 
DB 4160100                      
valid from:  24.05.2012 
 
 
Originator: ROKR / PDC
 
approved:  HESC / PDC 
Document: 
DB4160100EN 
Page 1 of 1 
All rights reserved acc. to DIN ISO 16016.  
PD 0019/2.2_11.10EN 
Application 
 
These multi standard wiring cables SC2.1 are UL, CSA and HAR (VDE)* approved and are designed for use for control cabi-
net  wiring  as  well  as  for  installation  in  protective  tubes,  applicable  within  the  scope  of  the  UL-  or  Canadian  or  European 
standard specifications. They are especially qualified for wiring in industrial machines in accordance with NFPA 79. At room 
temperature they are widely resistant to oils. 
Application range:  
HAR: 
Wiring cable for internal wiring acc. to HD 516 resp. VDE 0298-300 
 
(UL) MTW: 
Acc. to ANSI/NFPA 70 (National Electrical Code) 
 
UL (AWM): 
Oil resistant wiring cable for internal wiring 
 
CSA (TEW): 
Oil resistant wiring cable for internal wiring of devices 
 
Design 
 
Design / Approvals  
H07V-K ◄HAR► (*) acc. to HD 21.3 S3+A1 resp. VDE 0281-3   
 
(UL) MTW acc. to UL 1063 
 
UL (AWM) Style 1015 acc. to UL 758 
 
CSA (TEW) acc. to C22.2 No. 127 
 
*For the dimensions 0.5; 0.75; 1.0 and 16 mm² and the colours GN, YE, BU/WH and WH/BU there is no HAR-approval  
  available (X07V-K)! 
 
Conductor 
fine-wired core of tinned copper strands acc. to IEC 60228 resp. VDE 0295, Class 5 
 
 
UL 758 and CSA C22.2 
 
Core insulation 
special PVC based compound 
 
 
Electrical properties 
 
Nominal voltage  
HAR U
0
/U:   
450 / 750 V 
 
UL/CSA:      
600 V 
 
 
Test voltage  
 
2500 V AC 
 
 
 
 
 
Mechanical and thermal properties 
 
Min. bending radius  
fixed installation: 
OD≤8 mm: 
4 x OD** / 2 x OD*** 
 
 
8<OD≤12 mm:  5 x OD** / 3 x OD*** 
 
 
OD>12 mm: 
6 x OD** / 4 x OD*** 
 
** at conventional usage; *** at cautious bending 
 
Temperature range 
fixed installation:   
HAR: 
 -40 °C up to  +70 °C max. conductor temp. 
 
 
(UL) MTW: 
 -40 °C up to  +90 °C max. conductor temp.
 
 
UL (AWM)/CSA (TEW):  -40 °C up to +105 °C max. conductor temp. 
 
Flame resistance  
HAR:  
IEC 60332-1-2 resp. VDE 0482-332-1-2  
 
(UL) MTW and 
 
      UL (AWM):   
VW-1
 
 
 
CSA :  
FT1 
 
Oil resistance 
UL/CSA:  
60°C oil rating  
 
Tests                                 
acc. to IEC 60811, EN 50395, EN 50396, UL 1581 and CSA C22.2 
 
EC-Directives 
This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive) and 
 
ECD 2002/95/EC (RoHS, Restriction of the use of certain hazardous substances).