Lappkabel 4180502, Single Core Wiring Cable, , AWG, Blue Sheath 4180502 Data Sheet
Product codes
4180502
U.I. Lapp
GmbH
DATA SHEET
Multi-Standard SC 1
DB 4180400
valid from: 07.10.2010
Originator: R. Krämer / PDC
approved: H. Schillinger / PDC
Document:
DB4180400EN
page 1 of 1
All deviations from this specification are subject to explicit consent of U.I. Lapp GmbH. All rights reserved acc. to DIN 34.
PD 0019/2.1_11.09EN
Application
These multi standard wiring cables SC1 are UL, CSA and HAR (VDE) approved and are designed for use for control cabinet
wiring as well as for installation in protective tubes, applicable within the scope of the UL- or Canadian or European standard
specifications. At room temperature they are widely resistant to oils.
Application range:
HAR:
Wiring cable for internal wiring acc. to HD 516 resp. VDE 0298-300
UL (AWM):
Oil resistant wiring cable for internal wiring
CSA (AWM): Oil resistant wiring cable for internal wiring
Design
Design / Approvals
H05V-K ◄HAR► acc. to HD 21.3 S3+A1 resp. VDE 0281-3
UL (AWM) Style 1007 / 1569 acc. to UL 758
CSA (AWM I A/B) acc. to C22.2 No. 210-05
Conductor
fine-wired core of tinned copper strands acc. to IEC 60228 resp. VDE 0295, Class 5
UL 758 and CSA C22.2
Core insulation
special PVC based compound
Electrical properties
Nominal voltage
HAR U
0
/U: 300 / 500 V
UL/CSA: 300 V
Test voltage
2000 V AC
Mechanical and thermal properties
Min. bending radius
fixed installation:
4 x outer diameter at conventional usage
2 x outer diameter at cautious bending
Temperature range
fixed installation:
HAR: -40 °C up to +70 °C max. conductor temp.
UL/CSA: -40 °C up to +105 °C max. conductor temp.
Flame resistance
HAR:
IEC 60332-1-2 resp. VDE 0482-332-1-2
UL (AWM): VW-1
CSA :
FT1
Oil resistance
UL (AWM): 60°C oil rating
CSA (AWM I A/B) acc. to C22.2 No. 210-05
Tests
acc. to IEC 60811 resp. VDE 0473 and VDE 0472, UL 1581 and CSA C22.2
EC directive
This cable is conform to ECD 2006/95/EC (Low Voltage Directive).