Lappkabel 1600119, H07RN-F Cable, 3 x 4 mm², Black Sheath 1600119 Data Sheet

Product codes
1600119
Page of 1
DATA SHEET 
1600xxx 
 
RUBBER INSULATED CABLE H07RN-F 
valid from : 
12.01.2007
 
 
elaborated by:
 
TE-K:     H.Schillinger /  M. Herb 
Document: 
DB1600199EN 
page 1 of 1 
 
Nr.: 0019/0894 
 
 
Application 
 
H07RN-F is a heavy duty rubber sheathed cable for use on heavy appliance such as tool and agricultural 
machinery subject to high levels of stress in premises exposed to dry and damp conditions as well as in the 
open air and wet industrial environments. Continuous, busy movements, usage of these cables in moving 
cable carriers, respectively on motor drum guidance or under a strain of more than 15 N/mm² is not allowed.  
Assembly of rubber insulated cables (only the single core cable H07RN-F) in acc. to VDE 0282 part 4 they 
are recognized as short-circuit and earth-fault proof in acc. to VDE 0100 part 520. 
 
 
Design 
in acc. to HD 22.4 S4 that is VDE 0282 part 4
 
 
Conductor 
copper, fine wire strand in accordance to IEC 60228 that is VDE 0295,  
 
class 5 
 
Core insulation 
rubber compound EI4 in acc. to HD 22.1 that is VDE 0282 part 1 
 
Identification 
in acc. to VDE 0293-1, with up to 5 cores are coloured-coded in acc. to       
HD 308 S2 that is VDE 0293-308; cables with more than 7 cores black cores 
with white numbers with gn/ye ground conductor in acc. to  DIN EN 50334 
that is VDE 0293 part 334 
 
Outer sheath 
rubber compound EM2 in acc. to HD 22.1 that is VDE 0282 part 1 
 
Colour outer sheath 
black 
 
 
Electrical properties at 20° C 
 
Nominal voltage 
450 / 750 V 
 
Test voltage 
2500 V AC 
 
Mechanical and thermal properties 
 
 
Temp. range 
for fixed installation and handling: -25 up to + 60° C max. conductor 
temperature 
 
Min. bending radius 
for flexible use: 6 x cable diameter 
 
Flame retardant 
in acc. to IEC 60332-1-2 resp. VDE 0482 part 332-1-2 
 
Approvals 
H07RN-F in acc. to HD 22.4 S4 that is VDE 0282 part 4 
 
Tests 
in acc. to VDE 0472 and IEC 60811-x.x that is VDE 0473 
 
 
The cable is indicated with the 
HAR
 sign or a tracer thread. 
 
EC directive 
this cable confirms to ECD 73/23/EEC (low voltage directive).