Phoenix Contact Test disconnect terminal block URTK 6 3026272 3026272 Data Sheet

Product codes
3026272
Page of 19
Nov 9, 2013    1 / 19
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Test disconnect terminal block, Connection method: Screw connection, Cross section: 0.5 mm² -10
mm² , AWG: 20 - 10, Width: 8.2 mm, Mounting type: NS 35/7,5, NS 35/15, NS 32, Color: gray
 
Product Features
 The URTK 6 test disconnect terminal block and the UGSK 6 slide-type terminal block were developed specifically for use in current
transformer secondary circuits
 Can be fitted on both sides with fixed and switchable bridges as well as test sockets with 4 mm diameter
Key commercial data
package_quantity
50
GTIN
4017918168056
Technical data
General
Number of levels
1
Number of connections
2
Color
gray
Insulating material
PA
Inflammability class according to UL 94
V0
General
Rated surge voltage
6 kV
Pollution degree
3
Surge voltage category
III
Insulating material group
I
Connection in acc. with standard
IEC 60947-7-1
Nominal current I
N
41 A
Nominal voltage U
N
400 V
Open side panel
ja
Shock protection test specification
DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection
guaranteed
Finger protection
guaranteed
Surge voltage test setpoint
7.3 kV
Result of surge voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV